Plan Review Notes For Permit 18101252 |
Permit Number |
18101252 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-11-16 13:58:51 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION SIGNED AND | | SEALED BY THE ENGINEER: | | | | TYPICALLY, THIS TYPE OF STRUCTURE IS PRE-MANUFACTURED | | AND LABELED WITH PROOF OF INSPECTION FROM SITE WHERE | | MANUFACTURED. THIS LEAVES, IN ADDITION TO CHECKING THE | | LABEL FOR COMPLIANCE, ONLY A FOUNDATION INSPECTION | | WHICH IS COMMONLY COMPLETED USING HELICAL PILES AND | | STRAPS. | | | | 1. SUBMIT AN ENGINEERED SIGNED AND SEALED FOUNDATION | | PLAN, REGARDLESS OF HELICAL PILES OR REINFORCED | | CONCRETE FOOTINGS. | | 2. SUBMIT ENGINEERED SIGNED AND SEALED PLANS FOR THE | | STRUCTURAL ELEMENTS (FLOOR, WALLS, & ROOF FRAMING) | | INCLUDING CALCULATIONS. | | 3. SUBMIT PRODUCT APPROVALS FOR DOORS, WINDOWS, AND | | ROOFING SYSTEM. | | 4. A SUB-PERMIT WILL BE REQUIRED FOR ANY ELECTRICAL, | | MECHANICAL, OR PLUMBING THAT WILL BE INSTALLED. | | | | ALSO, THE COMMENTS FROM THE ZONING PLAN REVIEW NEED TO | | BE ADDRESSED. |
|