Plan Review Notes For Permit 18101151 |
Permit Number |
18101151 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-26 10:52:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) THE SUBMITTED SPEC SHEET INDICATES THAT THE MINIMUM | | WIRE SIZE SHALL BE 14AWG. THE PLAN SHEET DOES NOT | | INDICATE THE EXISTING WIRE SIZE. | | | | PLEASE REVIEW AND ENSURE THE EXISTING WIRE SIZE IN | | 14AWG MINIMUM. | | | | THE FIRE INSPECTOR SHALL VERIFY ON INSPECTION. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|