2019-01-22 17:03:402ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT ADDRESSED
 THERE ARE MAJOR DESIGN FLAWS IN THIS PLAN I I'M
 REQUESTING A MEETING WITH THE DESIGN PROFESSIONAL TO GO
 OVER COMMENTS. SEE CONTACT INFO BELOW.
  
 1. THE SANITARY FROM THE NEW BATHROOM SHALL NOT
 DISCHARGE TO THE RECLAIMED WATER SYSTEM IT SHALL
 DISCHARGE DIRECTLY TO CITY SEWER. PER FBC PL 301.3
  
 2.THE NEW BATHROOM FIXTURE SHALL BE CONNECTED TOGETHER
 AND VENTED BY THE LAVATORY. PER FBC PL 912.1
  
 3. PLEASE SHOW CITY SEWER ON SITE PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 4. A TRAP PRIMER IS REQUIRED ON ANY NEW FLOOR DRAINS.
 PER FBC PL 1002.4.1
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 PER FBC PL 416.5
  
 6. PROVIDE WATER ISOMETRIC OF NEW BATHROOM INCLUDING
 WATER HEATER . PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 7. SHOW LOCATION OF WATER HEATER ON THE FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1
  
 8. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDE FOR THE WATER HEATER IT SHALL COMPLY WITH FBC
 ENERGY TABLE 404.2
  
 9. THE SITE PLAN SHOWS A PROPOSED WATER METER LOCATION
 IF THEY ARE INSTALLING A NEW METER A NEW BACKFLOW WILL
 BE REQUIRED PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT
 WILL BE REQUIRED FOR THE NEW BACKFLOW. PER WPB
 UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  