2018-12-17 09:05:05 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE SANITARY FROM THE NEW BATHROOM SHALL NOT |
| DISCHARGE TO THE RECLAIMED WATER SYSTEM IT SHALL |
| DISCHARGE DIRECTLY TO CITY SEWER. PER FBC PL 301.3 |
| |
| 2.THE NEW BATHROOM FIXTURE SHALL BE CONNECTED TOGETHER |
| AND VENTED BY THE LAVATORY. PER FBC PL 912.1 |
| |
| 3. PLEASE SHOW CITY SEWER ON SITE PLAN. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 4. A TRAP PRIMER IS REQUIRED ON ANY NEW FLOOR DRAINS. |
| PER FBC PL 1002.4.1 |
| |
| 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. |
| PER FBC PL 416.5 |
| |
| 6. PROVIDE WATER ISOMETRIC OF NEW BATHROOM INCLUDING |
| WATER HEATER . PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 7. SHOW LOCATION OF WATER HEATER ON THE FLOOR PLAN. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 8. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION |
| GUIDE FOR THE WATER HEATER IT SHALL COMPLY WITH FBC |
| ENERGY TABLE 404.2 |
| |
| 9. THE SITE PLAN SHOWS A PROPOSED WATER METER LOCATION |
| IF THEY ARE INSTALLING A NEW METER A NEW BACKFLOW WILL |
| BE REQUIRED PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT |
| WILL BE REQUIRED FOR THE NEW BACKFLOW. PER WPB |
| UTILITIES DEPT. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |