2018-12-10 15:05:59 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18101134 |
| REVIEWED: DECEMBER 10, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. COVER SHEET STATES THE USE AS MERCHANTILE. |
| [FBC 304] LISTS CARWASH AS BUSINESS GROUP. |
| PLEASE BASE OCCUPANCY AND LOAD CALCULATIONS ON |
| BUSINESS. |
| |
| 2. SHEET SP-2 SHOWS THREE NEW CONCRETE PADS AT EACH NEW |
| DOOR. SHEET A-1 SHOWS PADS ON NEW STORE ONLY. IS THERE |
| A PAD AT THE ADA RESTROOM? UPDATE TO MATCH. |
| HOW ARE THESE TWO NEW AREAS ACCESIBLE WITH PROPOSED |
| STEP FROM LANDINGS OF 5.5 INCHES? |
| [FBC A402.1]PROVIDE ACCESSIBLE ROUTE FROM PARKING LOT |
| (BOTH NEW AREAS) |
| |
| 3. [FBC 107.3.5]SHEET A-4 SHOW DETAILS 3/A4 AND 4/A4 |
| SHOW EXISTING CEILING ABV. NEW FRAMED CEILING. SHEET |
| A-1 SAYS DROP CEILING. PLEASE CLARIFY WHAT IS EXISTING |
| STRUCTURE THAT NEW WALLS ARE CONNECTING TO, WHAT TYPE |
| OF CEILING IS IT AND CONNECTORS BEING USED TO CONNECT |
| TO EXISTING? |
| |
| 4. [FBC ENERGY C401.2]ENERGY COOLING CALCULATIONS WERE |
| MADE FOR 350 SQ. FT. THE NEW A/C AREA IS 280 ACCORDING |
| TO COVER SHEET. PLEASE ADJUST ENERGY CALCULATIONS FOR |
| AREA WITH A/C AT 280. |
| |
| 5. [FL.STATUTE 553.842]PRODUCT APPROVAL FOR STOREFRONT |
| SYSTEM IS EXPIRED. |
| PLEASE PROVIDE UPDATED VERSION FOR NOA 16-0208.13. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |