2018-11-26 06:59:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. VALUE FOR PRICE OF 3 WALL SIGNS LOW. PROVIDE |
| CONTRACT SIGNED BY BOTH OWNER AND CONTRACTOR TO INCLUDE |
| ALL MATERIALS AND LABOR. FBC 109.3 BUILDING PERMIT |
| VALUATION. FOR PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; |
| EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET |
| BY THE BUILDING OFFICIAL. |
| |
| 2. MIXING OF HIGH VOLTAGE AND LOW VOLTAGE TOGETHER IN |
| JBOX WITH BRANCH CIRCUIT WIRING NOT PERMITTED. PROVIDE |
| CORRECTION. NEC 725.136B |
| |
| 3. NO DISCONNECT SWITCH WITHIN SIGHT OF SIGN TO |
| DISCONNECT ALL BRANCH CIRCUIT CONDUCTORS BEFORE IT |
| ENTERS SIGN AS PER NEC 600.6A1 |
| |
| 4. ELECTRICIAN REQUIRED FOR NEW BRANCH CIRCUIT FOR SIGN |
| AND DISCONNECT. REFERENCE PERMIT NUMBER OF ELECTRICAL |
| PERMIT APPLIED FOR BY ELECTRICIAN IN PLAN REVIEW |
| COMMENTS REBUTTAL LETTER. |
| |
| SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| SPECIALTY CONTRACTOR) |
| |
| THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| VOLTS MAXIMUM. |
| |
| 5. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| PLEASE CALL MY CELL PHONE FOR ANY QUESTIONS OR |
| CLARIFICATIONS. 5616571653 |
| |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |
| |