Plan Review Notes For Permit 18101126 |
Permit Number |
18101126 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-12-12 16:16:36 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ACCESSIBLE PARKING SPACES AND ACCESS AISLE | | STRIPING DOES NOT COMPLY WITH CITY ORDINANCE SEC. | | 94-484 AND FBC ACCESSIBILITY 502.6.1 | | | | 2) PROVIDE DETAILS FOR THE ACCESSIBLE PARKING | | IDENTIFICATION SIGNS. FBC-A 502.6 | | | | 3) PROVIDE ELEVATIONS, SLOPES AND CROSS SLOPES. FBC | | 107.2.1 AND FBC-A 402 | | | | 4) PROVIDE DIMENSIONS OF THE CURB RAMP, CURB RAMP | | LANDINGS AND CURB RAMP FLARES. SHOW THAT IT COMPLIES | | WITH FBC-A 406 |
|