Plan Review Notes For Permit 18101112 |
Permit Number |
18101112 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-01-10 11:17:56 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL SHEETS PROVIDED BY ELECTRICAL CONTRACTOR | | CONFLICT WITH SHEETS PROVIDED BY DESIGN PROFESSIONAL. | | CORRECT ANY DISCREPANCIES. SCOPE OF WORK ON ELECTRICAL | | SHEETS VERSUS THE REFLECTED CEILING PLAN DOES NOT | | APPEAR TO RECONCILE. PROVIDE CORRECTIONS AND PROVIDE | | DETAIL SCOPE OF WORK. IF ELECTRICAL PANEL IS TO BE | | REPLACED OR RELOCATED, SHOW LOCATION. WPB FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|