Plan Review Notes
Plan Review Notes For Permit 18101028
Permit Number 18101028
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-10-31 14:26:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ENSURE THAT A FLOOR DRAIN IS INSTALLED IN THE PUMP
 ROOM.
  
 PER NFPA 20
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
 PLEASE ENSURE A FLOOR DRAIN IS INSTALLED. THE FIRE
 INSPECTOR WILL CONFIRM ON FIRE INSPECTION.
  
  
  
 2) THE MECHANICAL/ELECTRIC ROOM DOOR OPENS INTO AN EXIT
 ACCESS CORRIDOR. PLEASE ENSURE THIS DOOR HAS A
 AUTOMATIC DOOR CLOSER INSTALLED.
  
 THE FIRE INSPECTOR WILL CONFIRM ON FIRE INSPECTION.
  
  
  
  