Plan Review Notes For Permit 18101028 |
Permit Number |
18101028 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-31 14:26:54 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | | | 1) ENSURE THAT A FLOOR DRAIN IS INSTALLED IN THE PUMP | | ROOM. | | | | PER NFPA 20 | | | | 4.12.7* DRAINAGE. | | 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE | | OF ESCAPING | | WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, | | DRIVER, CONTROLLER, AND SO FORTH. | | 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED | | WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE | | LOCATION. | | | | PLEASE ENSURE A FLOOR DRAIN IS INSTALLED. THE FIRE | | INSPECTOR WILL CONFIRM ON FIRE INSPECTION. | | | | | | | | 2) THE MECHANICAL/ELECTRIC ROOM DOOR OPENS INTO AN EXIT | | ACCESS CORRIDOR. PLEASE ENSURE THIS DOOR HAS A | | AUTOMATIC DOOR CLOSER INSTALLED. | | | | THE FIRE INSPECTOR WILL CONFIRM ON FIRE INSPECTION. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|