Plan Review Notes For Permit 18100919 |
Permit Number |
18100919 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-22 18:21:08 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | HOW IS THE LIGHTING TO BE DONE IN THE DIFFERENT ROOMS | | OR IS THIS GOING TO BE OPEN TO EXISTING CEILING? | | | | NOTES SAY THAT THIS WILL BE PLUGIN TO EXISTING OUTLETS | | PLEASE ELABORATE ON HOW THIS WILL BE ACOMPLISHED. | | | | HOW WILL EXIT AND EMERGENCY LIGHTS BE WIRED INTO THE | | SHOW? | | | | PLANS SHOW SOME KIND OF TRUSS SYSTEM FOR LIGHTING, THIS | | WAS NOT EXISTING IN OLD STORE.(?) | | | | SHOW RISER WITH FEEDER OR BRANCH CIRCUITS TO DIMMER | | RACKS |
|