Plan Review Notes
Plan Review Notes For Permit 18100919
Permit Number 18100919
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-22 18:21:08FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 HOW IS THE LIGHTING TO BE DONE IN THE DIFFERENT ROOMS
 OR IS THIS GOING TO BE OPEN TO EXISTING CEILING?
  
 NOTES SAY THAT THIS WILL BE PLUGIN TO EXISTING OUTLETS
 PLEASE ELABORATE ON HOW THIS WILL BE ACOMPLISHED.
  
 HOW WILL EXIT AND EMERGENCY LIGHTS BE WIRED INTO THE
 SHOW?
  
 PLANS SHOW SOME KIND OF TRUSS SYSTEM FOR LIGHTING, THIS
 WAS NOT EXISTING IN OLD STORE.(?)
  
 SHOW RISER WITH FEEDER OR BRANCH CIRCUITS TO DIMMER
 RACKS