2018-10-23 11:29:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THE SUBMITTED PLAN SHEETS ARE TOO SMALL AND
 UNREADABLE AND AS A RESULT AN OFFICIAL PLAN REVIEW CAN
 NOT BE COMPLETED WITH ANY ACCURACY OR CONFIDENCE.
  
 PLEASE ENLARGE AND RESUBMIT
  
  
  
 2) A SCOPE OR WORK COULD NOT BE IDENTIFIED. IS THIS A
 FIRE LINE ASSEMBLY? IS IT A NEW INSTALL? IS THIS A
 RELOCATION?
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND SCOPE OF
 WORK.
  
  
  
 3) THERE ARE NO INDICATIONS OF COMPLIANCE WITH NFPA 24
 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE
 MAINS AND THEIR APPURTENANCES 2013 EDITION, IF
 APPLICABLE PER # 2.
  
 PLEASE ENSURE COMPLIANCE WITH, BUT NOT LIMITED TO,
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES.
 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW
 PREVENTION
 ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 INSTALLATION INSTRUCTIONS.
 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED,
 THEY
 SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE
 NEEDED.
  
 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE
 OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M)
 FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR
 VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH
 SECTION 6.4
 (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT
 LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW
 PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT AND COMPLIANCE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  