2018-12-04 15:00:10 | 1ST REVIEW |
| COMMENTS: DENIED |
| |
| 1. DOES THE REMODELING OF THE BATHROOMS REQUIRE FIXTURE |
| RECONFIGURATION? PLEASE CLARIFY PER WPB FBC 107.2.1. |
| 2. IF BATHROOM FIXTURES ARE RECONFIGURED THEN PROVIDE |
| THE FOLLOWING: |
| A. A SANITARY RISER DIAGRAM IS REQUIRED PER WPB FBC |
| 107.2.1. |
| B. PROVIDE DETAILED FLOOR PLAN SHOWING ANY REQUIRED |
| PARTITIONING FOR THE SHOWER AND PROVIDE SHOWER |
| DIMENSIONS CONFORMING TO FBC RES 2708.1; SHOW MINIMUM |
| COMPARTMENT CLEAR AND UNOBSTRUCTED ACCESS AND EGRESS |
| OPENING AS REQUIRED BY FBC RES P2708.1.1. INDICATE |
| WHETHER OR NOT THERE IS TO BE A SHOWER DOOR (IF SO, IT |
| MUST CONFORM TO FBC RES 2708.1). PROVIDE THE LOCATION |
| OF THE CONTROL VALVE PER WPB FBC 107.2.1. |
| C. PROVIDE DETAILED FLOOR PLAN SHOWING COMPLIANCE WITH |
| MINIMUM SPACE REQUIREMENTS IN ACCORDANCE WITH FBC RES |
| P2705.1.5 WATER CLOSETS AND LAVATORIES. A WATER CLOSET, |
| LAVATORY OR BIDET SHALL NOT BE SET CLOSER THAN 15 |
| INCHES (381 MM) FROM ITS CENTER TO ANY SIDE WALL, |
| PARTITION OR VANITY OR CLOSER THAN 30 INCHES (762 MM) |
| CENTER-TO-CENTER BETWEEN ADJACENT FIXTURES. THERE SHALL |
| BE A CLEARANCE OF NOT LESS THAN 21 INCHES (533 MM) IN |
| FRONT OF A WATER CLOSET, LAVATORY OR BIDET TO ANY WALL, |
| FIXTURE OR DOOR. |
| 3. PROVIDE FULL PERMIT VALUATION INCLUDING PLUMBING |
| COST PER WPB FBC 109. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |