Date |
Text |
2018-12-05 11:09:41 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18100882 |
| REVIEWED: DECEMBER 5, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC 107.2.1]ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| PLEASE ADD NAME AND SIGNATURE OF DESIGNER TO THE PLANS. |
| |
| 2. [FBC TABLE R602.3(3)NAIL SHEATHING TO MEET CURRENT |
| SPACING PER TABLE WHERE REPLACING. |
| WHAT EXISTING SUBSTRATE IS NEW SIDING BEING NAILED |
| INTO? WHAT THICKNESS? |
| A) VERTICAL SPACING OF SUPPORTING MEMBERS THAT |
| SHEATHING ATTACHES TO? |
| B) HOW MUCH AREA OF SIDING IS BEING REPLACED? |
| C) WHAT IS BEING INSTALLED FOR VAPOR BARRIER? |
| D) WHAT TYPE, SIZE AND AMOUNT OF CONNECTOR OF PER PIECE |
| OF NEW SIDING? |
| |
| NOTE: |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |