Plan Review Notes For Permit 18100875 |
Permit Number |
18100875 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-31 11:27:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | 1) THE SUBMITTED PLANS DO NOT INDICATE CLEARLY WHERE | | THE FENCE IS BEING PLACED. | | | | IT APPEARS THE FENCE SURROUNDS THE ENTIRE SITE. | | | | | | PLEASE CLEARLY INDICATED ALL THE LOCATION OF THE FENCE. | | | | | | | | | | 2) THE SUBMITTED PLANS DO NOT CLEARLY SHOW THE | | CONSTRUCTION AREA AND HOW THE EXITING OF THE BUILDING | | OR SPACES WILL BE AFFECTED. | | | | PLEASE REVIEW AND PROVIDE A LIFE SAFETY PLAN SHOWING | | THE EXITS OF THE BUILDING IN RELATION TO THE FENCE | | LOCATIONS. | | | | | | | | 3) THE SUBMITTED PLANS DO NOT SHOW AREAS ON HOW THE | | FIRE DEPARTMENT CAN ACCESS THE BUILDING, LOCATIONS OF | | FDC AND THEIR ACCESS. | | | | THE FD REQUIRES 20' FIRE LANE ACCESS TO THE BUILDING. | | | | PLEASE REVIEW AND PROVIDE DETAILS ON HOW AND WHERE THE | | FD WILLL ACCESS THE SITE AND BUILDING. | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|