Plan Review Notes
Plan Review Notes For Permit 18100875
Permit Number 18100875
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-10-31 11:27:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THE SUBMITTED PLANS DO NOT INDICATE CLEARLY WHERE
 THE FENCE IS BEING PLACED.
  
 IT APPEARS THE FENCE SURROUNDS THE ENTIRE SITE.
  
  
 PLEASE CLEARLY INDICATED ALL THE LOCATION OF THE FENCE.
  
  
  
  
 2) THE SUBMITTED PLANS DO NOT CLEARLY SHOW THE
 CONSTRUCTION AREA AND HOW THE EXITING OF THE BUILDING
 OR SPACES WILL BE AFFECTED.
  
 PLEASE REVIEW AND PROVIDE A LIFE SAFETY PLAN SHOWING
 THE EXITS OF THE BUILDING IN RELATION TO THE FENCE
 LOCATIONS.
  
  
  
 3) THE SUBMITTED PLANS DO NOT SHOW AREAS ON HOW THE
 FIRE DEPARTMENT CAN ACCESS THE BUILDING, LOCATIONS OF
 FDC AND THEIR ACCESS.
  
 THE FD REQUIRES 20' FIRE LANE ACCESS TO THE BUILDING.
  
 PLEASE REVIEW AND PROVIDE DETAILS ON HOW AND WHERE THE
 FD WILLL ACCESS THE SITE AND BUILDING.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  