2018-12-11 11:31:10 | PERMIT HAS BEEN SEPARATED FROM MASTER SO CONTRACTOR CAN |
| KEEP APPOINTMENT WITH FPL JLEAHY |
2018-12-04 09:18:25 | 1) REMOVE ALL OLD DOCUMENTS FROM THIS REVIEW PACKAGE |
| AND COMPILE THE PLANS INTO TWO CCOMPLETE SETS FOR |
| REVIEW. THERE ARE CURRENTLY 4 COPIES OF PLANS & |
| SPECIFICATIONS IN THE PERMIT PACKAGE. WPB AMEND. TO FBC |
| SECS. 107.1, 107.2.1. |
| 2) SHOW THE SIZE OF THE UNDERGROUND PE LINE TO THE |
| GENERATOR ON THE REVISED GAS DRAWING. |
| 3) SIZE THE GAS LINE DOWNSTREAM OF THE REGULATOR FOR |
| THE COOKTOP AND SHOW THE DISTANCE FROM THE REGULATOR TO |
| THE APPLIANCE AND THE TYPE OF PIPE. |
| 4) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE |
| INSTALLED WITHIN ONE (1) FOOT OF EITHER SIDE OF THE MP |
| REGULATOR. 2017 FBC-RESIDENTIAL SEC. G2421.2 (7), 2017 |
| FBC-FUEL GAS SEC. 410.2 (7). |
| 5) SHOW THE LOCATION OF THE MP REGULATORS FOR THE |
| TANKLESS WATER HEATER AND THE DRYER. |
| 6) SHOW THE TYPE OF PIPE TO THE GAS DRYER. |
| 7) SHOW THE DISTANCE FROM THE GAS METER TO THE MOST |
| REMOTE REGULATOR ON THE SYSTEM. 2017 FBC-FUEL GAS |
| SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, |
| G2413.4.2. |
| 8) THE GENERATOR SHALL BE LOCATED A MINIMUM 10 FEET |
| FROM ALL BUILDING OPENINGS UNLESS THE MANUFACTURER'S |
| INSTALLATION MANUAL ALLOWS A LESSER DISTANCE. |
| 9) THE GENERATOR SPECS SHOW THE MAXIMUM BTU LOAD OF THE |
| GENERATOR AS 281,000 YET THE GAS DRAWING SHOWS THE |
| GENERATOR BTU LOAD AS 330,000. CLARIFY. |
| |
| NOTE: CITY RECORDS DO NOT SHOW ANY PREVIOUS PERMITS FOR |
| GAS INSTALLATION AT THIS ADDRESS.THE EXISTING SYSTEM |
| AND APPLIANCES CAN EITHER BE INCLUDED IN THIS SCOPE OF |
| WORK OR A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| EXISTING SYSTEM. SOMEONE NEEDS TO ADDRESS THIS ISSUE |
| AND SUBMIT A RESPONSE AS TO WHAT ACTION WILL BE TAKEN. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |