Plan Review Notes
Plan Review Notes For Permit 18100818
Permit Number 18100818
Review Stop E
Sequence Number 2
Notes
Date Text
2019-01-11 06:16:39ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO SPECS OR LISTING PROVIDED FOR ACUTAL ELEVATOR
 UNIT ITSELF. PROVIDE LISTING/CERTIFICATIONS MODEL
 NUMBER ETC, FBC 107.2.1 NEC 90.7 110.2
  
 2. REBUTTAL COMMENT STATING MASTER DRAWING IS BEING
 "REVISED" WILL NOT SUFFICE. PROVIDE SIGNED ELECTRICAL
 DRAWING SHOWING CONDUIT SIZE/WIRING METHODS, WIRE SIZE,
 OVER CURRENT PROTECTION OF CIRCUIT, LOCATION OF
 RECEPTACLE IN HOME FOR ELEVATOR, LOCATION OF ELEVATOR
 ETC. FBC 107.2.1 FS 481.229; WPB FBC 107.3.5.1.2
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  