Plan Review Notes For Permit 18100770
Permit Number 18100770
Review Stop B
Sequence Number 4
Notes
Date Text
2018-12-05 14:33:45ALEX SUBMITTED RAS 117 CALCULATIONS VIA E-MAIL.
  
 INFORMATION SUBMITTED DOESN'T ADDRESS PREVIOUS
 COMMENTS. SEE COPY OF COMMENTS BELOW. CONTACT ME TO
 COORDINATE.
  
  
 ORIGINAL COMMENT:
 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED.
 CALCULATIONS FOR CORNER AREAS IS INCORRECT. THE
 SPECIFIED DESIGN-PRESSURES ARE -132.6 PSF BUT MAX.
 FASTENER SPACING CALCULATIONS ARE DONE FOR 110.7 PSF.
 REVISE AS REQUIRED. REVISE NUMBER OF REQUIRED ROWS
 ACCORDINGLY. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 THE CALCULATIONS WERE REVISED, BUT THE BASE SHEET
 FASTENING INFORMATION WAS NOT REVISED. THE NUMBER OF
 ROWS NEED TO BE REVISED ALSO. SEC. R301.1
 FBC-RESIDENTIAL.
  
  