2018-10-23 17:34:32 | RESIDENTIAL (R3) RE-ROOF THIRD SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| |
| |
| ORIGINAL COMMENT: |
| 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED. |
| CALCULATIONS FOR CORNER AREAS IS INCORRECT. THE |
| SPECIFIED DESIGN-PRESSURES ARE -132.6 PSF BUT MAX. |
| FASTENER SPACING CALCULATIONS ARE DONE FOR 110.7 PSF. |
| REVISE AS REQUIRED. REVISE NUMBER OF REQUIRED ROWS |
| ACCORDINGLY. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| THE CALCULATIONS WERE REVISED, BUT THE BASE SHEET |
| FASTENING INFORMATION WAS NOT REVISED. THE NUMBER OF |
| ROWS NEED TO BE REVISED ALSO. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| |