2018-10-23 17:34:32RESIDENTIAL (R3) RE-ROOF THIRD SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 ORIGINAL COMMENT:
 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED.
 CALCULATIONS FOR CORNER AREAS IS INCORRECT. THE
 SPECIFIED DESIGN-PRESSURES ARE -132.6 PSF BUT MAX.
 FASTENER SPACING CALCULATIONS ARE DONE FOR 110.7 PSF.
 REVISE AS REQUIRED. REVISE NUMBER OF REQUIRED ROWS
 ACCORDINGLY. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 THE CALCULATIONS WERE REVISED, BUT THE BASE SHEET
 FASTENING INFORMATION WAS NOT REVISED. THE NUMBER OF
 ROWS NEED TO BE REVISED ALSO. SEC. R301.1
 FBC-RESIDENTIAL.
  
  