2018-10-17 13:47:44RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED.
 CALCULATIONS FOR CORNER AREAS IS INCORRECT. THE
 SPECIFIED DESIGN-PRESSURES ARE -132.6 PSF BUT MAX.
 FASTENER SPACING CALCULATIONS ARE DONE FOR 110.7 PSF.
 REVISE AS REQUIRED. REVISE NUMBER OF REQUIRED ROWS
 ACCORDINGLY. SEC. R301.1 FBC-RESIDENTIAL.
  
 2- THE MINIMUM DISTANCE FOR EDGE AND CORNER AREAS IS 4
 FEET NOT 3 FEET AS REQUIRED BY NOTE "A" ON FIGURE
 R301.2(7) FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3- IT LOOKS-LIKE THERE IS A TYPO ON THE ASCE REFERENCE.
 THE CORRECT REFERENCE IS ASCE 7-10 NOT ASCE 7-0.10 .
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
  
  