Plan Review Notes For Permit 18100770 |
Permit Number |
18100770 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-17 13:47:44 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED. | | CALCULATIONS FOR CORNER AREAS IS INCORRECT. THE | | SPECIFIED DESIGN-PRESSURES ARE -132.6 PSF BUT MAX. | | FASTENER SPACING CALCULATIONS ARE DONE FOR 110.7 PSF. | | REVISE AS REQUIRED. REVISE NUMBER OF REQUIRED ROWS | | ACCORDINGLY. SEC. R301.1 FBC-RESIDENTIAL. | | | | 2- THE MINIMUM DISTANCE FOR EDGE AND CORNER AREAS IS 4 | | FEET NOT 3 FEET AS REQUIRED BY NOTE "A" ON FIGURE | | R301.2(7) FBC-RESIDENTIAL. REVISE AS REQUIRED. | | | | 3- IT LOOKS-LIKE THERE IS A TYPO ON THE ASCE REFERENCE. | | THE CORRECT REFERENCE IS ASCE 7-10 NOT ASCE 7-0.10 . | | REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|