Plan Review Notes For Permit 18100705 |
Permit Number |
18100705 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-02-05 09:48:58 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- REVISE INSTALLATION. ACCORDING TO INSTALLATION | | SCHEDULE ON SHEET 12 OF 20 THE ANCHOR SPACING FOR | | TAPCONS IS LESS THAN 10" FOR SHUTTERS THAT HAVE A SPAN | | GREATER THAN 72". REVISE AS REQUIRED. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | 2- REVISE INSTALLATION SCHEDULE. THE SHUTTER SPAN IS | | INCORRECT. THE SHUTTER SPAN IS THE LENGTH OF THE | | SHUTTER. SEE TYPICAL SHUTTER ELEVATION ON SHEET 5 OF 20 | | AND REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|