2019-01-23 15:45:42 | BUILDING REVIEW APPROVED WITH PROVISO: |
| |
| NOTE: |
| THERE ARE SOME PRODUCT APPROVALS THAT WERE CHANGED FROM |
| PREVIOUS REVIEWS. I TOLD DAVID BOWDEN TO TAKE BACK ALL |
| PRODUCT APPROVALS AND RESUBMIT ONLY THE ONES THAT ARE |
| GOING TO BE INSTALLED TO AVOID CONFLICTS/DELAYS. ALSO, |
| I TOLD HIM TO IDENTIFY ON ALL PRODUCT APPROVALS THE |
| LOCATION OF PRODUCT APPROVALS SUBMITTED. FOR EXAMPLE, |
| ENTRY DOOR, STAIRWAY WINDOWS, ETC. |
| |
| 1-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| |
| A) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE |
| INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS. NOTE: |
| FLINTASTIC MODIFIED BITUMEN ROOF SYSTEM PRODUCT |
| APPROVAL FL16709-R4 SPECIFIED ON BALCONY FLOOR |
| CONSTRUCTION DETAIL ON SHEET A-010 IS NOT GOOD FOR |
| CERAMIC TILE. |
| |
| B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON |
| PLANS/ELEVATIONS. |
| |
| C) CASEMENT WINDOWS SIZE AS SPECIFIED ON WINDOW |
| SCHEDULE. SEE PLANS/ELEVATIONS. |
| |
| D)OUTSWING ENTRY DOORS WITH SIDELITES AS SHOWN ON |
| PLANS/ELEVATIONS. |
| |
| E) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY |
| SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| WITH THE CALCULATED DESIGN PRESSURES. |
| |
| 2) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 3- ENERGY CALCULATIONS SUBMITTED (RESCHECK): |
| A) LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR IS REQUIRED. |
| B) BLOWER DOOR TEST WILL BE REQUIRED. |