2018-10-30 11:52:54 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NOTE 54 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES AND CONFLICTS |
| WITH NOTE IN ANOTHER AREA. PROVIDE CORRECTION. NEC |
| 406.12; FBC RE E4002.14 |
| 2. AFCI PROTECTION SHOWN IN NOTE 58 IS NOT CODE |
| COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902 |
| 3. RISER DIAGRAM SHOWS (3) 3/0 CONUCTORS TO FPL FROM |
| METER. THIS WIRE SIZE IS NOT RATED AS REQUIRED THE |
| SERVICE. PROVIDE CORRECTION. FBC RE E3603.1.1 |
| 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3606.3 |
| 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| NEC 110.3, 110.9; FBC RE E3603.3 |
| 6. IN MASTER BATH THE LIGHTING OVER THE TUB AND SHOWER |
| APPEAR TO BE A MOUNTED LIGHT FIXTURE. NO PARTS OF |
| CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR |
| CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR |
| CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN |
| A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET |
| VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER |
| STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D); FBC |
| RE E4003.11 |
| 7. IN MASTER BATH, A GFCI PROTECTED RECEPTACLE OUTLET |
| ON A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH |
| BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); |
| FBC RE E3703.4, E3901.6 |
| 8. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 |
| 9. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. THE SWITCH MUST BE LOCATED IN THE |
| INTERIOR OF THE STRUCTURE TO CONTROL A LIGHTING OUTLET |
| ON THE EXTERIOR. SWITCH IS CURRENTLY SHOWN ON THE |
| EXTERIOR OF STRUCTURE. PROVIDE CORRECTION. NEC |
| 210.70(A)(2)(B), FBC RE E3903.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |