2018-10-17 08:04:02 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| REVISION IS DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC-R - M 1602.3 PROVIDE BALANCED AIR RETURN AT THE |
| MASTER BEDROOM SUITE. THE 10" DIAMETER TRANSFER DUCT |
| FROM THE MASTER BEDROOM SUITE IS TOO SMALL. BASED ON |
| FBCR-M1602.3 IT APPEARS THAT A 14" DIAMETER TRANSFER |
| DUCT IS REQUIRED. SEE CODE REQUIREMENTS BELOW. |
| M1602.3 BALANCED RETURN AIR. RESTRICTED RETURN AIR |
| OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL |
| ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE |
| RETURN GRILL OR WHEN CEILING SPACES ARE USED AS RETURN |
| PLENUMS AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE |
| PORTION OF THE RETURN PLENUM TO ANOTHER. PROVISIONS |
| SHALL BE MADE IN BOTH RESIDENTIAL AND COMMERCIAL |
| BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND PRESSURE |
| DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE |
| DIFFERENTIALS ACROSS CLOSED DOORS WHERE RETURNS ARE |
| CENTRALLY LOCATED SHALL BE LIMITED TO 0.01 INCH WC (2.5 |
| PASCALS) OR LESS. PRESSURE DIFFERENTIALS ACROSS FIRE |
| WALLS IN CEILING SPACE PLENUMS SHALL BE LIMITED TO 0.01 |
| INCH WC (2.5 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR |
| AIR TRANSFER PATHWAYS FROM THE HIGH PRESSURE ZONE TO |
| THE LOW ZONE. |
| EXCEPTIONS: |
| 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR |
| SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER |
| RETURN AIR BALANCE. |
| 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (32 258 |
| MM2) (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR |
| SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING AN |
| UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO |
| ACHIEVE PROPER RETURN AIR BALANCE. |
| 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE |
| REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, |
| EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL |
| BE INCLUDED. |
| |
| 2) THE SIGNED AND SEALED PLANS THAT WERE SUBMITTED HAVE |
| BEEN CHANGED USING WHITEOUT. THIS IS NOT ACCEPTABLE PER |
| CITY AMENDMENTS 107.2.1.3. HAVE THE ARCHITECT REDRAW |
| THE PLANS WITH THE CORRECTIONS AND SIGN AND SEAL THEM |
| AS REQUIRED BY FAC 61G1-16.003 |
| |
| |