2018-10-26 15:25:24PLAN DENIED
 1) GREASE DUCT NOT SHOWN ON PLAN, SHOW EXHAUST AND
 SUPPLY DUCT FOR HOOD ON PLAN.
 SECTION 107 FBC 2017
 2) SEPARATE APPLICATION AND PLANS REQUIRED FOR HOOD AND
 ANSOL SYSTEM
 3) REFER TO SECTION 107.2.1 ARCHITECT MUST SEAL AND
 SIGN PLANS.
 4) PROVIDE TWO SETS OF HOOD PLANS AND TWO SETS OF PLANS
 FOR ANSOL SYSTEM.
  