2018-10-17 09:56:49PERMIT # 18100665
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) TWO SEPERATE PERMITS ARE NEEDED FOR THIS SCOPE OF
 WORK. ONE PERMIT FOR THE HOOD EXHAUST SYSTEM AND ONE
 FOR THE HOOD SUPPRESSION SYSTEM. EACH PERMIT SHALL
 INDICATE THE SPECIFIC VALUE FOR THE SCOPE OF WORK.
  
 2) PLANS ARE MARKED AS "FOR REFERENCE ONLY". PERMITS
 SHALL BE FOR OFFICIAL USE AND NOT AS "REFERENCE ONLY".
 PLEASE REMOVE.
  
 3) HOOD SUPPRESSION DRAWINGS SHALL INCLUDE THE PRODUCT
 SPECIFICATIONS AND SPEC SHEETS FOR THE DEVICES AND
 NOZZLES USED. ALSO, INCLUDE ACCURATE LAYOUT OF
 EQUIPMENT BEING PROTECTED (EX. FRYERS, GRIDDLES, ETC.)
  
 3) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  