Plan Review Notes
Plan Review Notes For Permit 18100657
Permit Number 18100657
Review Stop E
Sequence Number 2
Notes
Date Text
2018-11-19 05:33:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INITAL PERMIT FEE SUBMITTED WAS $20000. CONTRACTOR
 WAS ASKED FOR SIGNED CONTRACT. SCOPE OF WORK PROVIDED
 IN CONTRACT DOES NOT MATCH SCOPE OF WORK ON PLANS.
 PROVIDE ACCURATE PLANS AND AN UP TO DATE CONTRACT.
 CONTRACT SAYS SA- X10, SB X2
  
 PLANS SAY SB X1, SA X5, CA X10. FBC 107.2.1
  
 2. NO LOAD CALCULATION PROVIDED, NO OCP PROVIDED FOR
 PANEL FEEDING SITE LIGHTS., ACCURATE LOAD CALCULATION
 INCLUDING ALL LOADS. NEC 220, FBC 107.2.1
  
 3. PROVIDE EXTERIOR AUTOMATIC LIGHTING CONTROL FOR SITE
 LIGHTING AS PER FBC CE 405.2.4 MUST BE ASTRONOMICAL
 TIME CLOCK WITH 10/HR BATTERY BACKUP. A NOTE ON DRAWING
 WILL SUFFICE.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  