2018-11-19 05:33:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. INITAL PERMIT FEE SUBMITTED WAS $20000. CONTRACTOR |
| WAS ASKED FOR SIGNED CONTRACT. SCOPE OF WORK PROVIDED |
| IN CONTRACT DOES NOT MATCH SCOPE OF WORK ON PLANS. |
| PROVIDE ACCURATE PLANS AND AN UP TO DATE CONTRACT. |
| CONTRACT SAYS SA- X10, SB X2 |
| |
| PLANS SAY SB X1, SA X5, CA X10. FBC 107.2.1 |
| |
| 2. NO LOAD CALCULATION PROVIDED, NO OCP PROVIDED FOR |
| PANEL FEEDING SITE LIGHTS., ACCURATE LOAD CALCULATION |
| INCLUDING ALL LOADS. NEC 220, FBC 107.2.1 |
| |
| 3. PROVIDE EXTERIOR AUTOMATIC LIGHTING CONTROL FOR SITE |
| LIGHTING AS PER FBC CE 405.2.4 MUST BE ASTRONOMICAL |
| TIME CLOCK WITH 10/HR BATTERY BACKUP. A NOTE ON DRAWING |
| WILL SUFFICE. |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |