 *****NOTE:
 01/15/2020 MEETING W/ SAMANTHA HILL, JORGE GONZALEZ
 (ENG'R) AND DANIEL ACEVEDO (CONTR) TO GO OVER COMMENTS.
 JG.
  
  
  
 RESIDENTIAL (R3) SIXTH BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SHEET S-01:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIALL.
  
 RESPONSE:
 REPEAT COMMENT (SIX TIMES). REVISED DRAWING SUBMITTED
 THIS TIME ON SHEET S-01 DOESN'T PROVIDE ANY DETAIL OR
 SPECIFICATIONS FOR AN APPROVED ONE HOUR FIRE RATED
 FLOOR /CEILING ASSEMBLY COMPLYING WITH THE REQUIREMENTS
 OF SEC. R302.3 FBC-RESIDENTIAL. THE PREVIOUS PLANS
 SPECIFIED APPROVED ASSEMBLY NO L501 BUT IT WAS NOT
 COORDINATED WITH THE BUILDING SECTION ON SAME SHEET.
 THE COMMENT WAS FOR ENGINEER TO COORDINATE THE
 INFORMATION. NOW ENGINEER PROVIDES A NEW DRAWING THAT
 DOESN'T PROVIDE ANY ONE HOUR APPROVED FIRE RATED
 ASSEMBLY. NEED TO PROVIDE DETAIL/SPECIFICATIONS FOR AN
 APPROVED 1 HOUR FLOOR/CEILING ASSEMBLY THAT IS TESTED
 IN ACCORDANCE WITH ASTM E119 OR UL 263 AS REQUIRED BY
 SEC. R302.3 FRBC-RESIDENTIAL.
  
 THIS PLAN REVIEW HAVE BEEN DENIED SIX TIMES FOR THIS
 SAME ITEM. ENGINEER OF RECORD TO PAY FOUR TIMES THE
 PLAN REVIEW FEE ($1630.72) AS REQUIRED BY FLORIDA
 STATUTE 553.80(2)(B).
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 2- WINDOW REPLACEMENT:
 A) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REPEAT COMMENT (SIX TIMES). EGRESS NOTE ON SHEET A-01
 DOESN'T ADDRESS THE COMMENT. THIS NOTE DOESN'T ANSWER
 WHAT IT WAS REQUESTED. PLEASE READ THE COMMENT AGAIN
 AND PROVIDE THE REQUIRED INFORMATION. ALSO, IT LOOKS
 LIKE THE CODE SECTION IS TAKING FROM ANOTHER CODE OTHER
 THAN THE 2017 FBC-RESIDENTIAL. IN ADDITION, THE WINDOW
 SIZES SHOWN ON THE PROPOSED WINDOW SCHEDULE DON'T
 COMPLY.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT (SIX TIMES). FLORIDA PRODUCT APPROVAL
 COVER PAGE WAS NOT PROVIDED. NEED TO PROVIDE COMPLETE
 FLORIDA PRODUCT APPROVAL, INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO THE DRAWINGS
 SUBMITTED. THE FLORIDA PRODUCT APPROVAL IS REQUIRED
 BECAUSE IT SHOWS IF PRODUCT IS APPROVED AND CURRENT
 CODE IN EFFECT.
 NOTE: IF THERE IS NOT CURRENT FLORIDA PRODUCT APPROVAL,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 2 COPIES OF COMPLETE ENGINEERED PACKAGE WITH ORIGINAL
 SEAL/SIGNATURE ALONG WITH APPLICATION FOR PRODUCT
 APPROVAL WILL BE REQUIRED FOR BUILDING OFFICIAL
 REVIEW/APPROVAL PROCESS.
  
 4- RAFTER CONNECTION DETAIL ON SHEET S-01. ENGINEER TO
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 SPECIFIED CONNECTION IS ADEQUATE FOR THE SUPPORT OF
 SECOND FLOOR JOISTS. ENGINEER TO SHOW THAT 1/4" X
 3-1/4" TAPCONS SPACED AT 24" O.C ARE ADEQUATE TO CARRY
 ALL LIVE AND DEAD LOADS. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 RESPONSE:
 SCOPE OF WORK IS NO CLEAR NOW. SEC. 107.2.1 CITY
 AMENDMENTS. NEW STRUCTURAL DRAWING S-01 SHOWS WHAT
 LOOKS LIKE A SECOND FLOOR FRAMING PLAN (THERE IS NO
 NAME FOR THIS PLAN). IN ADDITION IT DOESN'T SPECIFY
 WHAT IS THE SCOPE OF WORK ON THIS PLAN. PREVIOUS FLOOR
 FRAMING PLAN WAS FOR THE REPAIR ON ONE CORNER OF THE
 FLOOR. NOW, THE SCOPE OF WORK IS NOT CLEAR.
 ALSO, PREVIOUS SET OF PLANS SHOWED A ROOF FRAMING PLAN
 FOR REPAIR AT ONE CORNER ALSO. THE STRUCTURAL PLAN
 SUBMITTED (S-01) IS NOT CLEAR ON THE SCOPE OF WORK.
  
 ON THE OTHER HAND, WALL SECTIONS ON THE RIGHT HAND SIDE
 OF THE SHEET SHOWS THE SECOND FLOOR CONCRETE BLOCK WALL
 BEING SUPPORTED BY WOOD FLOOR JOISTS. THIS DOESN'T SEEM
 TO BE RIGHT. ( MASONRY SHALL NOT BE SUPPORTED ON WOOD.
 SEC. 2104.1.1 FBC-BUILDING). PREVIOUS DRAWINGS SHOWED A
 CONTINUOUS CONCRETE BLOCK WALL ALL THE WAY UP TO THE
 SECOND FLOOR. AND, FLOOR JOISTS WERE SUPPORTED ON
 STRUCTURAL WOOD LEDGERS. CLARIFY/REVISE AS REQUIRED.
 ALSO, THE HURRICANE TIES (SIMPSON H3) SPECIFIED FOR THE
 FIRST FLOOR FRAMING PLAN AND ROOF FRAMING PLAN ARE WOOD
 TO WOOD CONNECTORS. ACCORDING TO WALL SECTIONS
 SUBMITTED THERE ARE WOOD JOISTS ATTACHED TO THE
 CONCRETE BLOCK WALL. REVISE AS REQUIRED. SPECIFY
 CONNECTORS FOR MASONRY CONSTRUCTION.
 AND, THERE IS NOT INFORMATION ABOUT THE ROOF VENTS.
 PREVIOUS DRAWINGS SHOWED CONTINUATIONS ROOF VENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 5- ALL PLANS SUBMITTED HAVE A COPY OF THE SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD. NEED TO PROVIDE
 PLANS WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 61G15-23.001 FAC.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS
 REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES
 AND TO HELP EXPEDITE THE REVIEW PROCESS.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED
 SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
  