2019-06-26 09:46:25 | 09/18/19 MET WITH RONEN HAZAN (OWNER),DANIEL ACEVEDO |
| (CONTRACTOR), JOHN FRASCA (CODE ENFORCEMENT) TO GO OVER |
| COMMENTS. JG. |
| |
| |
| |
| RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| |
| |
| 1- SHEET S-01: |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE |
| HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND |
| B. |
| SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. DETAIL FOR 1 HOUR FLOOR ASSEMBLY AND |
| INFORMATION SHOWN ON THE BUILDING SECTION FOR THE |
| FLOOR/CEILING ASSEMBLY ON SAME SHEET DON'T MATCH. |
| REVISE AS REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. THERE IS NO COORDINATION |
| BETWEEN 1 HOUR FLOOR ASSEMBLY NO L501 AND INFORMATION |
| SHOWN ON THE WALL SECTION ON SAME SHEET. |
| |
| PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR THE APPROVED |
| FLOOR /CEILING FIRE RATED ASSEMBLY. SPECIFY ALL |
| FINISHES, INCLUDING THE FINISH FLOOR. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| ENGINEER IS NOT PROVIDING A COMPLETE DRAWING OF THE 1 |
| HOUR APPROVED FLOOR/CEILING FIRE RATED ASSEMBLY. |
| PROVIDE COMPLETE UL L501 APPROVED ASSEMBLY DETAIL THAT |
| MATCHES PROPOSED INSTALLATION. SPECIFY THICKNESS OF |
| MATERIALS, FASTENING SPECIFICATIONS, ETC. TYPICALLY |
| THIS IS DONE BY COPYING THE DETAILS FROM THE UL |
| WEBSITE. |
| |
| 2- WINDOW REPLACEMENT : |
| A) CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS |
| AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY |
| COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 |
| FBC-EXISTING BUILDING. |
| |
| RESPONSE: |
| REPEAT COMMENT. EGRESS NOTE ON SHEET A-01 DOESN'T |
| ADDRESS THE COMMENT. THIS NOTE DOESN'T ANSWER WHAT IT |
| WAS REQUESTED. PLEASE READ THE COMMENT AGAIN AND |
| PROVIDE THE REQUIRED INFORMATION. ALSO, IT LOOKS LIKE |
| THE CODE SECTION IS TAKING FROM ANOTHER CODE OTHER THAN |
| THE 2017 FBC-RESIDENTIAL. IN ADDITION, THE WINDOW SIZES |
| SHOWN ON THE PROPOSED WINDOW SCHEDULE DON'T COMPLY. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE |
| FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO |
| DRAWINGS MA-FL0211-17 SUBMITTEDD. |
| |
| RESPONSE: |
| REPEAT COMMENT. FLORIDA PRODUCT APPROVAL COVER PAGE WAS |
| NOT PROVIDED. NEED TO PROVIDE COMPLETE FLORIDA PRODUCT |
| APPROVAL, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE THAT CORRESPONDS TO THE DRAWINGS SUBMITTED. THE |
| FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS |
| IF PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. |
| NOTE: IF THERE IS NOT CURRENT FLORIDA PRODUCT APPROVAL, |
| THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. |
| 2 COPIES OF COMPLETE ENGINEERED PACKAGE WITH ORIGINAL |
| SEAL/SIGNATURE ALONG WITH APPLICATION FOR PRODUCT |
| APPROVAL WILL BE REQUIRED FOR BUILDING OFFICIAL |
| REVIEW/APPROVAL PROCESS. |
| |
| 4- RAFTER CONNECTION DETAIL ON SHEET S-01. ENGINEER TO |
| PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE |
| SPECIFIED CONNECTION IS ADEQUATE FOR THE SUPPORT OF |
| SECOND FLOOR JOISTS. ENGINEER TO SHOW THAT 1/4" X |
| 3-1/4" TAPCONS SPACED AT 24" O.C ARE ADEQUATE TO CARRY |
| ALL LIVE AND DEAD LOADS. SEC. 107.2.1.2 CITY |
| AMENDMENTS. |
| |
| 5- SPECIFICATIONS SUBMITTED ON A SEPARATE LETTER BY THE |
| ENGINEER OF RECORD FOR THE REPAIR OF RAFTERS IN MAIN |
| HOUSE DON'T MATCH DETAILS SHOWN ON THE STRUCTURAL |
| DRAWINGS. ENGINEER TO COORDINATE AND PROVIDE ALL THE |
| SPECIFICATIONS ON THE STRUCTURAL PLANS TO AVOID |
| CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS |
| REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER |
| ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES |
| AND TO HELP EXPEDITE THE REVIEW PROCESS. |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED |
| SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD |
| DRAWINGS FOR REFERENCE. |
| |
| |