2019-02-21 18:12:18RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
  
 1- SHEET S-01:
  
 ORIGINAL COMMENT:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE
 HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND
 B.
 SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) CLARIFY WHY PROVIDING ONE HOUR FIRE RATED DEMISING
 PARTITION ON THESE SHEET. THERE ARE NO DEMISING
 PARTITIONS BETWEEN DWELLING UNITS. THE REQUIRED FIRE
 RATING SEPARATION IS LOCATED ON THE FLOOR/CEILING
 ASSEMBLY. COORDINATE WITH ITEM #1(A) ABOVE. PROVIDE
 WALL DETAIL/SPECIFICATIONS THAT SHOW COMPLIANCE WITH
 THE FLOOR/CEILING ASSEMBLY PENETRATIONS AS REQUIRED BY
 SEC. R302.4 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT.
 2- ROOF TRUSS REPAIR DETAILS ON SHEET S-02 ARE
 INCOMPLETE. SEC. 107.2.1 CITY AMENDMENTS.
 A)SPECIFY NAIL TYPE AND HOW LONG ARE THE 2X4'S THAT ARE
 SISTERED TO THE TRUSSES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) SPECIFY WHICH CONNECTOR IS GOING TO BE USED FOR THE
 ROOF TO WALL CONNECTIONS.
  
 RESPONSE:
 REPEAT COMMENT. DETAILS ARE KEYED WITH SOME CONNECTORS,
 BUT THERE IS NOT CONNECTOR SCHEDULE. REVISE AS
 REQUIRED.
  
 C) NEW SHEET S-02 WAS NOT SIGNED AND SEALED BY THE
 ENGINEER OF RECORD AS REQUIRED BY SEC. 471. F.S.
  
 ORIGINAL COMMENT:
 3- FLAT ROOF REPAIR DETAIL ON SHEET S-02 IS NOT CLEAR
 AND DOESN'T MATCH FRAMING PLAN SHOWN ON SAME SHEET.
 REVISE AS REQUIRED TO MATCH. ALSO, WHERE IS DETAIL 3
 S-01? SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 A)REPEAT COMMENT. THIS DETAIL WAS REDUCED AND PLACED
 UNDER THE ROOF TRUSS REPAIR DETAIL BOX BELOW. NOW THERE
 IS MORE CONFUSION OF WHAT DETAIL APPLIES TO. ALSO, IT'
 TOO SMALL AND IS NOT LEGIBLE. REVISE AS REQUIRED.
 PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS THAT APPLY
 TO THIS JOB. SEC. 107.2.1 CITY AMENDMENTS.
  
 NEW COMMENT:
 B) NEW FLAT ROOF SECTION DETAIL DOESN'T MATCH FLAT ROOF
 PLAN. AND, (1)ROOF SHEATHING NAILING SPECIFICATIONS IS
 NOT CLEAR. (2)PLYWOOD PANEL SIZE AND NAILING PATTERN
 DON'T SEEM TO MATCH LOCATION OF ROOF STRUCTURAL FRAMING
 MEMBERS. (3)SPECIFY ROOF SHEATHING NAIL TYPE.
 (4)CLARIFY HOW 4" X 20" @ 4' ROOF VENTS WILL PROVIDE
 CROSS VENTILATION ON A FLAT ROOF IF THERE IS NOT AIR
 SPACE IN BETWEEN THE ROOFING JOISTS TO ALLOW FOR CROSS
 VENTILATION?. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 4- DOORS AND WINDOWS CALCULATED DESIGN PRESSURES SHOWN
 ON SHEET A-01 ARE THE SAME FOR ALL OPENINGS. DESIGN
 PRESSURES SEEM TOO LOW FOR SOME OPENINGS. BASED ON THE
 ACTUAL OPENING EFFECTIVE AREA, WALL ZONE AND MEAN ROOF
 HEIGHT. PROVIDE THE ACTUAL DESIGN PRESSURES FOR EACH
 OPENING OR PROVIDE CALCULATIONS FOR WORST CASED
 SCENARIO THAT WILL COVER ALL OPENINGS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4(A)- REVISED SHEET A-01 WAS NOT SIGNED AND SEALED BY
 THE ENGINEER OF RECORD AS REQUIRED BY SEC. 471. F.S.
  
 ORIGINAL COMMENT:
 5- WINDOW REPLACEMENT :
 A)CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND
 TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 B) OK.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
  
 ORIGINAL COMMENT:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS MA-FL0211-17 SUBMITTED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 ORIGINAL COMMENT:
 C) FLAT ROOF NOA 16-0517.08. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA TO MEET THE DESIGN PRESSURES AT
 ALL ROOF ZONES.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
  
 8- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 ENGINEER OF RECORD TO CALL IF THERE ARE ANY QUESTIONS
 REGARDING THE COMMENTS AND PROVIDE A RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID ANY PLAN REVIEW FEES
 AND TO HELP EXPEDITE THE REVIEW PROCESS.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND REMOVE/VOID THE PREVIOUSLY REVIEWED
 SHEETS. PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER