2018-11-27 10:47:59 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1- SHEET S-01: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE |
| HOUR FIRE RATED FLOOR ASSEMBLY SEPARATING DUPLEX A AND |
| B. |
| SEC. 801.3 FBC-EXISTING BUILDING AND SEC. R302.3 |
| FBC-RESIDENTIAL. |
| |
| B) CLARIFY WHY PROVIDING ONE HOUR FIRE RATED DEMISING |
| PARTITION ON THESE SHEET. THERE ARE NO DEMISING |
| PARTITIONS BETWEEN DWELLING UNITS. THE REQUIRED FIRE |
| RATING SEPARATION IS LOCATED ON THE FLOOR/CEILING |
| ASSEMBLY. COORDINATE WITH ITEM #1(A) ABOVE. PROVIDE |
| WALL DETAIL/SPECIFICATIONS THAT SHOW COMPLIANCE WITH |
| THE FLOOR/CEILING ASSEMBLY PENETRATIONS AS REQUIRED BY |
| SEC. R302.4 FBC_RESIDENTIAL. |
| |
| 2- ROOF TRUSS REPAIR DETAILS ON SHEET S-02 ARE |
| INCOMPLETE. SEC. 107.2.1 CITY AMENDMENTS. |
| A)SPECIFY NAIL TYPE AND HOW LONG ARE THE 2X4'S THAT ARE |
| SISTERED TO THE TRUSSES. |
| B) SPECIFY WHICH CONNECTOR IS GOING TO BE USED FOR THE |
| ROOF TO WALL CONNECTION. |
| |
| 3- FLAT ROOF REPAIR DETAIL ON SHEET S-02 IS NOT CLEAR |
| AND DOESN'T MATCH FRAMING PLAN SHOWN ON SAME SHEET. |
| REVISE AS REQUIRED TO MATCH. ALSO, WHERE IS DETAIL 3 |
| S-01? SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- DOORS AND WINDOWS CALCULATED DESIGN PRESSURES SHOWN |
| ON SHEET A-01 ARE THE SAME FOR ALL OPENINGS. DESIGN |
| PRESSURES SEEM TOO LOW FOR SOME OPENINGS. BASED ON THE |
| ACTUAL OPENING EFFECTIVE AREA, WALL ZONE AND MEAN ROOF |
| HEIGHT. PROVIDE THE ACTUAL DESIGN PRESSURES FOR EACH |
| OPENING OR PROVIDE CALCULATIONS FOR WORST CASED |
| SCENARIO THAT WILL COVER ALL OPENINGS. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 5- WINDOW REPLACEMENT : |
| A)CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND |
| TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE |
| WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING |
| BUILDING. |
| NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD |
| SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR |
| EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE |
| EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY |
| SEC. 702.5. |
| |
| B) SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW |
| OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE |
| REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT |
| A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE |
| FINISHED FLOOR. CLEARLY SPECIFY IF THERE ARE ANY |
| WINDOWS WHERE THE WINDOW SILL IS LESS THAN 24" ABOVE |
| THE FINISH FLOOR. |
| SEC. 702.4 FBC-EXISTING BUILDING. |
| |
| 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| |
| A) EXTERIOR DOORS AS SHOWN ON PLANS. NOTE: PROVIDE |
| FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO |
| DRAWINGS MA-FL0211-17 SUBMITTED. |
| |
| B) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY |
| SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| WITH THE CALCULATED DESIGN PRESSURES. |
| |
| C) FLAT ROOF NOA 16-0517.08. PROVIDE SIGNED AND SEALED |
| RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION |
| #7 ON LAST PAGE OF NOA TO MEET THE DESIGN PRESSURES AT |
| ALL ROOF ZONES. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| |