2018-12-04 09:12:38 | 1ST REVIEW: |
| PLUMBING COMMENTS: DENIED |
| |
| 1. RE: PLAN SHEET E-1, SANITARY RISER DIAGRAM |
| A) MASTER BATH; THE DRY VENTS AT THE SHOWER AND THE TWO |
| LAVATORIES EXTEND HORIZONTALLY BEFORE RISING |
| VERTICALLY. THIS IS PROHIBITED PER FBC RES P3104.3. |
| B) MASTER BATH; THE FIXTURE DRAINS FOR THE SHOWER AND |
| BOTH LAVATORIES RISE VERTICALLY ABOVE THE VENT BEFORE |
| CONNECTING TO THE TRAP. THIS IS PROHIBITED PER FBC RES |
| P3105.2 AND P3201.5.3. |
| C) BATH #2; THE FIXTURE DRAIN FOR THE SHOWER RISES |
| VERTICALLY ABOVE THE VENT BEFORE CONNECTING TO THE |
| TRAP. THIS IS PROHIBITED PER FBC RES P3105.2 AND |
| P3201.5.3. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |