2018-12-03 13:58:11 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18100634 |
| REVIEWED: NOVEMBER 30, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL TO KEEP |
| CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| AND STORM DRAINS DURING CONSTRUCTION. |
| YOU CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE |
| PROTECTED TO THE DRAINAGE PLAN. |
| SOME ENGINEERING STANDARD DETAILS CAN BE USED FROM WPB |
| WEBSITE-POLLUTION CONTROL. |
| HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| /FORMS,-PERMITS-APPLICATIONS |
| |
| 2. [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE |
| DRAINAGE PLAN. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| THIS CAN BE SHOWN ON THE SITE PLAN THAT IS REQUESTED |
| FROM |
| |
| 3. [FBC R807]CO-ORDINATE ATTIC ACCESS SHOWN ON SHEET A1 |
| WITH TRUSS LAYOUT ON SHEET S2. SHEET A1 SHOWS ACCESS |
| CENTERED IN RROM, BUT SHEET S2 SHOWN TRUSS DOWN THE |
| CENTER OF ROOM. |
| |
| 4. [FBC R806.5]UNVENTED ATTIC AND UNVENTED ENCLOSED |
| RAFTER |
| ASSEMBLIES. UNVENTED ATTICS AND UNVENTED ENCLOSED ROOF |
| FRAMING ASSEMBLIES CREATED BY CEILINGS THAT ARE APPLIED |
| DIRECTLY TO THE UNDERSIDE OF THE ROOF FRAMING MEMBERS |
| AND |
| STRUCTURAL ROOF SHEATHING APPLIED DIRECTLY TO THE TOP |
| OF THE ROOF |
| FRAMING MEMBERS/RAFTERS, SHALL BE PERMITTED WHERE ALL |
| THE FOLLOWING |
| CONDITIONS ARE MET: |
| A. THE UNVENTED ATTIC SPACE IS COMPLETELY WITHIN THE |
| BUILDING THERMAL ENVELOPE. |
| SHEET A-3 NOTE SAYS FOAM INSULATION AND NO VENTS. IF NO |
| VENTS THE ATTIC SPACE NEEDS TO BE IN THE THERMAL |
| ENVELOPE. ICYNENE OR EQUIVALENT WOULD BE APPLIED UNDER |
| ROOF DECK. |
| IF IT IS TO BE ON THE ATTIC BOTTOM CHORD PROVIDE VENT |
| CALCULATIONS FOR THE ATTIC SPACE. |
| |
| 5. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES |
| REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH |
| THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD |
| INDEX AND SMOKE DEVELOPED INDEX. |
| |
| 6. [FBC R316.5.3]IF MECHANICAL EQUIPMENT IN THE ATTIC |
| SPACE THAN IT REQUIRES IGNITION BARRIER. IF AIR HANDLER |
| WILL BE IN ATTIC ADD NOTE FOR IGNITION BARRIER. |
| |
| 7. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL FOR |
| WINDOW MULL TO GO WITH SINGLE HUNG WINDOW NOA |
| 17-0630.08 |
| |
| 8. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO |
| THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| THIS WILL BE A PROVISO ITEM THAT DOES NOT NEED TO BE |
| ADDRESSED. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| |