Plan Review Notes
Plan Review Notes For Permit 18100634
Permit Number 18100634
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-03 13:58:11****CORRECTIONS****
 W.P.B. PERMIT: 18100634
 REVIEWED: NOVEMBER 30, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION.
 YOU CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN.
 SOME ENGINEERING STANDARD DETAILS CAN BE USED FROM WPB
 WEBSITE-POLLUTION CONTROL.
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 2. [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE
 DRAINAGE PLAN.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
 THIS CAN BE SHOWN ON THE SITE PLAN THAT IS REQUESTED
 FROM
  
 3. [FBC R807]CO-ORDINATE ATTIC ACCESS SHOWN ON SHEET A1
 WITH TRUSS LAYOUT ON SHEET S2. SHEET A1 SHOWS ACCESS
 CENTERED IN RROM, BUT SHEET S2 SHOWN TRUSS DOWN THE
 CENTER OF ROOM.
  
 4. [FBC R806.5]UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER
 ASSEMBLIES. UNVENTED ATTICS AND UNVENTED ENCLOSED ROOF
 FRAMING ASSEMBLIES CREATED BY CEILINGS THAT ARE APPLIED
 DIRECTLY TO THE UNDERSIDE OF THE ROOF FRAMING MEMBERS
 AND
 STRUCTURAL ROOF SHEATHING APPLIED DIRECTLY TO THE TOP
 OF THE ROOF
 FRAMING MEMBERS/RAFTERS, SHALL BE PERMITTED WHERE ALL
 THE FOLLOWING
 CONDITIONS ARE MET:
 A. THE UNVENTED ATTIC SPACE IS COMPLETELY WITHIN THE
 BUILDING THERMAL ENVELOPE.
 SHEET A-3 NOTE SAYS FOAM INSULATION AND NO VENTS. IF NO
 VENTS THE ATTIC SPACE NEEDS TO BE IN THE THERMAL
 ENVELOPE. ICYNENE OR EQUIVALENT WOULD BE APPLIED UNDER
 ROOF DECK.
 IF IT IS TO BE ON THE ATTIC BOTTOM CHORD PROVIDE VENT
 CALCULATIONS FOR THE ATTIC SPACE.
  
 5. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  
 6. [FBC R316.5.3]IF MECHANICAL EQUIPMENT IN THE ATTIC
 SPACE THAN IT REQUIRES IGNITION BARRIER. IF AIR HANDLER
 WILL BE IN ATTIC ADD NOTE FOR IGNITION BARRIER.
  
 7. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL FOR
 WINDOW MULL TO GO WITH SINGLE HUNG WINDOW NOA
 17-0630.08
  
 8. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
 THIS WILL BE A PROVISO ITEM THAT DOES NOT NEED TO BE
 ADDRESSED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  