Plan Review Notes For Permit 18100612 |
Permit Number |
18100612 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-16 13:20:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS ON ANY PLAN SHEET OF WHAT | | IS REVISED. | | | | PER NFPA 1 | | | | 1.14 PLAN REVIEW. | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | PLEASE REVIEW AND PROVIDE THE LOCATION AND DEVICES THAT | | REPRESENT AS-BUILTS. | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|