Plan Review Notes For Permit 18100586 |
Permit Number |
18100586 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-18 08:59:48 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18100586 | | REVIEWED: OCTOBER 11, 2018 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC ENERGY = FBC ENERGY CONSERVATION | | | | 1. [FBC 1503.4]PROVIDE EXISTING SCUPPERS SIZING TO MEET | | DRAINAGE REQUIREMENTS IN FBC PLUMBING CHAPTER 11. IF | | ROOF DRAINS SHOW LOCATIONS ON SKETCH. | | | | 2. [FBC 1505.1]PLEASE PROVIDE THE TYPE OF CONSTRUCTION | | AND THE FIRE CLASSIFICATION OF NEW ROOF SYSTEM. | | | | 3. [FBC 1508.1]PROVIDE ENGINEERING FOR THE NEW | | INSULATION ATTACHMNET (SEE NOTE #2 ON FL-11475-R8) | | | | 4. [FBC 1507.10.1]ADD MINIMUM ROOF SLOPE TO SKETCH. | | | | NOTE: | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | NEED "VOID", RENDERING THEM NOT USABLE. | | |
|