Plan Review Notes
Plan Review Notes For Permit 18100547
Permit Number 18100547
Review Stop M
Sequence Number 1
Notes
Date Text
2018-11-08 10:18:491ST REVIEW FBC-2017 MECHANICAL
 REVISION PERMIT #18100547
 11/8/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: THE O/A INTAKES ON THE WEST SIDE OF THE
 BUILDING ARE EXTENDING OUT FROM THE WALL AS SHOWN ON
 THE PLAN WHICH WILL REQUIRE ADDITIONAL DETAILS SHOWING
 HOW THEY WILL BE SUPPORTED AND ALSO HOW THE "WALL
 LOUVERS" THAT ARE CALLED OUT WILL BE INSTALLED- SECTION
 304.1 FBC M.
  
 2) M1.1: THE LOCATION OF THE O/A INTAKES APPEAR TO BE
 WITHIN 10' OF THE PARKING LOT WHICH IS PROHIBITED PER
 SECTION 401.4 FBC M.
  
 3) M1.1: CLARIFY HOW THE SUPPLY AIR FROM ROOMS 111,
 112, & 118 IS BEING RETURNED TO THE AIR HANDLERS.
 PLEASE NOTE THAT CORRIDORS SHALL BE USED AS A RETURN
 DUCT- SECTION 601.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  