2018-11-08 10:18:49 | 1ST REVIEW FBC-2017 MECHANICAL |
| REVISION PERMIT #18100547 |
| 11/8/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M1.1: THE O/A INTAKES ON THE WEST SIDE OF THE |
| BUILDING ARE EXTENDING OUT FROM THE WALL AS SHOWN ON |
| THE PLAN WHICH WILL REQUIRE ADDITIONAL DETAILS SHOWING |
| HOW THEY WILL BE SUPPORTED AND ALSO HOW THE "WALL |
| LOUVERS" THAT ARE CALLED OUT WILL BE INSTALLED- SECTION |
| 304.1 FBC M. |
| |
| 2) M1.1: THE LOCATION OF THE O/A INTAKES APPEAR TO BE |
| WITHIN 10' OF THE PARKING LOT WHICH IS PROHIBITED PER |
| SECTION 401.4 FBC M. |
| |
| 3) M1.1: CLARIFY HOW THE SUPPLY AIR FROM ROOMS 111, |
| 112, & 118 IS BEING RETURNED TO THE AIR HANDLERS. |
| PLEASE NOTE THAT CORRIDORS SHALL BE USED AS A RETURN |
| DUCT- SECTION 601.2 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |