Plan Review Notes
Plan Review Notes For Permit 18100527
Permit Number 18100527
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-15 13:36:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULE FOR MDP SHOWS SEVERAL PANELS THAT
 WERE NOT ORIGINALLY ON PLAN, INCLUDING PANEL LPB, PANEL
 G, PANEL H, PANEL D AND PANEL AC. THESE ITEMS ARE NOT
 SHOWN IN RISER DIAGRAM OR ON PLAN. PROVIDE CORRECTION.
 WPB FBC 107.2.1; NEC 215.5
 2. PROVIDE PANEL SCHEDULES AND LOAD INFORMATION FOR
 EACH PANEL MENTIONED IN COMMENT 1. NEC 210.19, 210.20,
 220, 408.4; WPB FBC 107.2.1
 3. NEW PANEL FOR BRAIN EXHIBIT IS NOT LABELED IN RISER
 DIAGRAM. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 215.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  