2018-10-29 12:19:371) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. SHOW THE BTU LOAD
 FOR THE EXISTING SYSTEM ON THE GAS RISER. FBC 107.2.1.
 2) SHOW THE SIZE OF THE PIPE TO THE EXISTING SYSTEM.
 FBC 107.2.1.
 3) SHOW THE SIZE OF THE PIPE AT THE OUTLET OF THE GAS
 METER. THIS SIZE MAY HAVE TO BE INCREASED BASED ON THE
 LONGEST RUN AND THE TOTAL BTU LOAD ON THE SYSTEM.
 4) THE SUBMITTED GAS PLAN SHOWS THE BTU LOAD FOR THE
 GENERATOR AT 750,000 BTU'S BUT THE GENERAC SPECS SHOW
 THE BTU LOAD AS 681,000 BTU'S . CLARIFY.
 5) PREVIOUS GAS PLAN ON FILE IN CITY RECORDS SHOWS THE
 DISTANCE TO THE FURTHEST OUTLET AT 202 FEET. THIS
 DISTANCE SHALL BE USED FOR THE SIZING OF THE GAS LINE
 TO THE GENERATOR, NOT 50 FEET AS SHOWN. 2017 FBC-FUEL
 GAS SEC.402.4.1. A MINIMUM SIZE OF 1 INCH PE IS
 REQUIRED TO THE GENERATOR. TABLE 402.4 (22).
 6) THE SIZE OF THE GALVANIZED LINE AT THE OUTLET OF THE
 GAS METER SHALL BE INCREASED TO 1 1/4 INCH PIPE PER
 TABLE 402.4 (5).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  