2018-10-12 11:20:49 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE ARE INDICATIONS THAT A DUCT DETECTOR WILL |
| CAUSE A FULL FIRE ALARM ACTIVATION. NFPA PROVIDES CODE |
| REFERENCES FOR SUPERVISORY SIGNAL ACTIVATION. |
| |
| PER NFPA 90A, 2015 ED. |
| |
| 6.4.3* FUNCTION. |
| 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2 |
| SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON |
| DETECTING THE PRESENCE OF SMOKE. |
| |
| 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE |
| AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A |
| BUILDING, THE SMOKE DETECTORS REQUIRED BY THE |
| PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE |
| FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS |
| OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING |
| CODE. |
| |
| 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING |
| DAMPERS OR FOR HEATING, VENTILATING, AND |
| AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED |
| TO ACTIVATE THE BUILDING EVACUATION ALARM. |
| |
| 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4 |
| ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN |
| APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE |
| FOLLOWING SHALL OCCUR: |
| (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4 |
| SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A |
| NORMALLY OCCUPIED AREA. |
| (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE |
| INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED |
| AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR |
| TROUBLE. |
| |
| PER NFPA 72, 2013 ED |
| 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS. |
| 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO |
| BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS |
| INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET |
| THE REQUIREMENTS OF 21.7.4. |
| 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC |
| SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL. |
| 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A |
| CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION |
| SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL. |
| 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM |
| SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES, |
| OR STANDARDS. |
| |
| PLEASE PROGRAM ACCORDINGLY FOR SUPERVISORY ACTIVATION. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |