Plan Review Notes For Permit 18100490 |
Permit Number |
18100490 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-15 08:24:39 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107, SCOPE NOT CLEAR. IS THE ROOF HATCH | | REPLACING AN EXISTING ROOF HATCH? | | | | 2. FBC B 1609, REVISE PLAN TO SHOW LOCATION OF ROOF | | HATCH. THIS HAS A DESIGN PRESSURE LIMITATION OF -70; | | CLEARLY INDICATE IN WHICH ZONE THIS IS PROPOSED. | | | | 3. FBC B 1609, THE ASSEMBLY SELECTED HAS A DESIGN | | PRESSURE LIMITATION OF -60PSF. PROVIDE CALCULATIONS FOR | | ZONES 2 AND 3 FASTENING, PREPARED BY A DESIGN | | PROFESSIONAL AS REQUIRED BY THE PRODUCT APPROVAL. | | | | 4. FBC 107, PROVIDE THE PAGES OF THE PRODUCT APPROVAL | | WHICH APPLY TO ALL ASSEMBLIES. | | | | |
|