2018-10-24 16:23:07 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1-SHUTTER MOUNTING CONDITION IS NOT CLEAR. CLEARLY |
| IDENTIFY/CIRCLE MOUNTING CONDITION FOR EACH OPENING |
| (BUILD OUT, WALL MOUNTED, FLOOR MOUNTED, TRUSS MOUNTED, |
| ETC) FOR PROPER REVIEW OF THE SHUTTERS INSTALLATION |
| SCHEDULE. . SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: C1 AS SHOWN ON THE INSTALLATION SCHEDULE ON |
| COLUMN 4 IS NOT A SHUTTER MOUNTING CONDITION. REVISE AS |
| REQUIRED. |
| |
| 2- CLARIFY THE SHUTTER SPAN SHOWN ON THE INSTALLATION |
| SCHEDULE ON COLUMN #6. ARE THESE PANELS INSTALLED |
| HORIZONTAL OR VERTICALLY. WHY THE SHUTTER SPAN IS THE |
| SAME AS THE OPENING SIZE?. WHAT'S THE SHUTTER SPAN FOR |
| OPENINGS #4 AND #6?. ARE ALL THE SHUTTERS GOING TO BE |
| ANCHORED TO CONCRETE OR ARE THEY GOING TO BE ANCHORED |
| TO HOLLOW CONCRETE BLOCK WITH FILLED CELLS. ANCHOR |
| SCHEDULE FOR HOLLOW CONCRETE BLOCK IS DIFFERENT. THAT'S |
| WHY IS IMPORTANT TO KNOW THE CORRECT SUBSTRATE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- IF USING THE ENGINEER WIND LOAD CALCULATIONS FROM |
| ENGINEERING EXPRESS, THEN THEY NEED TO HAVE ENGINEER'S |
| ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| FLORIDA STATE WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| NOTE: CONTRACTOR MAY USE THE TABLES R301.2(2) AND |
| R301.2(3) FBC-RESIDENTIAL TO DETERMINE THE WIND LOADS. |
| |
| |
| |