2018-10-24 16:23:07RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-SHUTTER MOUNTING CONDITION IS NOT CLEAR. CLEARLY
 IDENTIFY/CIRCLE MOUNTING CONDITION FOR EACH OPENING
 (BUILD OUT, WALL MOUNTED, FLOOR MOUNTED, TRUSS MOUNTED,
 ETC) FOR PROPER REVIEW OF THE SHUTTERS INSTALLATION
 SCHEDULE. . SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: C1 AS SHOWN ON THE INSTALLATION SCHEDULE ON
 COLUMN 4 IS NOT A SHUTTER MOUNTING CONDITION. REVISE AS
 REQUIRED.
  
 2- CLARIFY THE SHUTTER SPAN SHOWN ON THE INSTALLATION
 SCHEDULE ON COLUMN #6. ARE THESE PANELS INSTALLED
 HORIZONTAL OR VERTICALLY. WHY THE SHUTTER SPAN IS THE
 SAME AS THE OPENING SIZE?. WHAT'S THE SHUTTER SPAN FOR
 OPENINGS #4 AND #6?. ARE ALL THE SHUTTERS GOING TO BE
 ANCHORED TO CONCRETE OR ARE THEY GOING TO BE ANCHORED
 TO HOLLOW CONCRETE BLOCK WITH FILLED CELLS. ANCHOR
 SCHEDULE FOR HOLLOW CONCRETE BLOCK IS DIFFERENT. THAT'S
 WHY IS IMPORTANT TO KNOW THE CORRECT SUBSTRATE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- IF USING THE ENGINEER WIND LOAD CALCULATIONS FROM
 ENGINEERING EXPRESS, THEN THEY NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 NOTE: CONTRACTOR MAY USE THE TABLES R301.2(2) AND
 R301.2(3) FBC-RESIDENTIAL TO DETERMINE THE WIND LOADS.
  
  
  