Plan Review Notes For Permit 18100354 |
Permit Number |
18100354 |
|
Review Stop |
SIGNATURE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-04-30 09:46:38 | REVISED 5/6/19 | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. ARCHITECTURAL PAGES LACK THE ARCHITECT BUSINESS | | NUMBER (AAC001633). PLEASE ADD BUT ONLY RESUBMIT PAGES | | WHICH CHANGE DUE TO CODE RELATED COMMENTS. | | | | 2. CIVIL PAGES SIGNED BY RICHARD REIKENIS, PE LACK A | | SEAL AND LANGUAGE REQUIRED BY FAC61G15-23.004. THE | | SIGNATURE CAN BE REVISED TO STATE "SIGNED AND SEALED" | | OR A LEGIBLE IMAGE OF A SEAL IS TO BE INCLUDED. ALSO | | NOTE LANGUAGE REQUIRED. PLEASE ADDRESS BUT RESUBMIT | | PAGES ONLY WHICH CHANGE DUE TO CODE RELATED COMMENTS. | | | | 3. MEP PAGES (MICHAEL GUIDA, PE) DIGITAL SIGNATURE | | LACKS LANGUAGE REQUIRED BY FAC61G15-23.004. THE | | CERTIFICATE OF AUTHORIZATION (27754) IS REQUIQRED TO BE | | INCLUDED IN THE TITLE BLOCK. PLEASE ADDRESS BUT | | RESUBMIT ONLY PAGES WHICH CHANGE DUE TO CODE RELATED | | COMMENTS. | | | | 4. THE TITLE BLOCK FOR STRUCTURAL PAGES PREPARED BY | | HARLEY DAVIDSON, PE IS NOT CLEAR. IF PRACTICING | | ENGINEERING THROUGH MESCO BUILDING SOLUTIONS A | | CERTIFICATE OF AUTHORIZATION IS REQUIRED AND THE NUMBER | | IS TO BE INCLUDED IN THE TITLE BLOCK. | | | | THE LANGUAGE REQUIRED BY FACG1G15-23.004 IS REQUIRED. | | | | 5. FIRE SPRINKLER SIGNED BY JUAN E. REYES, PE IS NOT | | DIGITALLY SIGNED, FS471. | | | | | | | | | | | | | 2019-04-26 14:12:30 | ELECTRICAL SHEETS GOOD. |
|