2019-04-17 14:23:29 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL |
| MANUAL |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| 1. PLEASE NOTE THAT IN ACCORDANCE WITH THE PROVISIONS |
| OF FBC PL 403.3.3 (WHICH ADDRESSES LOCATION OF TOILET |
| FACILITIES WITH A PATH OF TRAVEL TO SUCH FACILITIES |
| SHALL NOT EXCEED A DISTANCE OF 500 FEET) AND BASED UPON |
| THE SUPPORTING DOCUMENTS PROVIDED IN THE THE |
| ARCHITECT'S RESPONSE LETTER DATED 1/24/19, NEW TOILET |
| FACILITIES ARE NOT REQUIRED IN THE NEW STRUCTURE. |
| HOWEVER, PER TABLE 403.1 AND NOTING THAT THE OCCUPANCY |
| LOAD OF THE NEW STRUCTURE IS GREATER THAN 15, A |
| DRINKING FOUNTAIN (CONFORMING TO THE REQUIREMENTS OF |
| FBC PL 410 AND FBC ACC 602) AND A SERVICE SINK IS |
| REQUIRED. |
| 2. PLEASE REFER TO C-2 PAVING AND GRADING PLAN AND |
| A-3.0 EXTERIOR ELEVATIONS. PER WPB FBC 107.2.1 PROVIDE |
| THE FOLLOWING. |
| A. RECONCILE DOWNSPOUT LOCATIONS BETWEEN THE TWO PLANS. |
| B. PROVIDE STORM DRAIN CALCULATIONS AND SIZING OF |
| GUTTERS AND DOWNSPOUTS. |
| 3. PER WPB FBC 107.2.1, REMOVE NON-APPLICABLE ITEMS |
| FROM THE FOLLOWING DRAWINGS; A1.1, P1.0 AND P2.0. |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |