Plan Review Notes
Plan Review Notes For Permit 18100354
Permit Number 18100354
Review Stop E
Sequence Number 2
Notes
Date Text
2019-04-26 15:46:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. LOAD CALCULATION SHOWS A DEMAND LOAD FOR KITCHEN
 EQUIPMENT AT 50%. I SEE NO KITCHEN EQUIPMENT THAT WOULD
 QUALIFY FOR A DEMAND LOAD REDUCTION. ALSO, A REDUCTION
 OF 50% FOR KITCHEN EQUIPMENT DOES NOT EXIST. PROVIDE
 CORRECTION. NEC 220.56 (THE LOAD CALCULATION IS STILL
 INCORRECT. THE DEMAD FACTOR APPLIED FOR RECEPTACLE
 LOADS IS NOT PERMITTED FOR ALL OF THESE LOADS. SOME OF
 THESE ARE NOT STANDARD RECEPTACLES FIGURED AT 180 VA
 PER STRAP. THE MOTOR LOADS SHOULD BE CALCULATED PER NEC
 220.14(C). PROVIDE CORRECTION.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE CLARIFICATION FOR FIRE SPRINKLER FEED, WILL
 THERE BE A FIRE SPRINKLER PUMP, OR IS THE WATER
 PRESSURE FROM CITY ACCEPTABLE AND A FIRE PUMP WILL NOT
 BE REQUIRED? IF FIRE PUMP REQUIRED, INCLUDE ELECTRICAL
 DETAILS. WPB FBC 107.2.1 (QUESTION NOT ANSWERED. AS THE
 REQUIREMENTS FOR A FIRE PUMP WOULD CHANGE THE DESIGN OF
 THE ELECTRICAL SERVICE, THIS INFORMATION IS REQUIRED.)
 7. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  