2019-05-06 13:53:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 1609, SHEET CS-1 DECLARES EXPOSURE C, SHEET A3.0 | | STATES THIS IS EXPOSURE B. NOTE THAT THIS APPEARS TO BE | | IN EXPOSURE C DUE TO THE PATCH CONDITION TO THE | | NORTHEAST. DESIGN PRESSURES APPEAR LOW (A-3.0). FOR | | INSTANCE, 21 SF, ZONE 5, +29.7/-38.7 PER PLAN; TABLE | | FOR EXPOSURE C, ZONE 5, MRH 20' REQUIRES +40.4/-54.1. | | CALCULATIONS MAY BE REQUIRED. | | | | SEE ALSO STRUCTURAL PAGE F4, EXPOSURE C WITH DESIGN | | PRESSURE OF +36/-48 REQUIRED FOR 10 SF. | | | | ARCHITECT WAS CONTACTED REGARDING A REDLINE. | | | | 2. SHEET A1.1 HAS DETAILS FOR THE BREAK ROOM; THIS | | SHEET HAS BEEN VOIDED. | | | | 3. THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | | A) ART IN PUBLIC PLACES: APPLICATION REQUIRED WITHIN 90 | | DAYS AFTER PERMIT ISSUANCE. | | | | |
|