2019-05-06 13:53:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 1609, SHEET CS-1 DECLARES EXPOSURE C, SHEET A3.0
 STATES THIS IS EXPOSURE B. NOTE THAT THIS APPEARS TO BE
 IN EXPOSURE C DUE TO THE PATCH CONDITION TO THE
 NORTHEAST. DESIGN PRESSURES APPEAR LOW (A-3.0). FOR
 INSTANCE, 21 SF, ZONE 5, +29.7/-38.7 PER PLAN; TABLE
 FOR EXPOSURE C, ZONE 5, MRH 20' REQUIRES +40.4/-54.1.
 CALCULATIONS MAY BE REQUIRED.
  
 SEE ALSO STRUCTURAL PAGE F4, EXPOSURE C WITH DESIGN
 PRESSURE OF +36/-48 REQUIRED FOR 10 SF.
  
 ARCHITECT WAS CONTACTED REGARDING A REDLINE.
  
 2. SHEET A1.1 HAS DETAILS FOR THE BREAK ROOM; THIS
 SHEET HAS BEEN VOIDED.
  
 3. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 A) ART IN PUBLIC PLACES: APPLICATION REQUIRED WITHIN 90
 DAYS AFTER PERMIT ISSUANCE.
  
  