2018-11-09 11:36:31 | FAILED |
| |
| PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| |
| 1) PROVIDE A SITE PLAN SHOWING THE SETBACKS OF THE |
| BUILDING FROM THE PROPERTY LINES. |
| |
| 2) THE PARKING LOT WILL REQUIRE SEPARATE PERMITTING. |
| PLEASE NOTE THAT THE DRIVE AISLE FOR THE 7 PARKING |
| SPACES AT THE NORTHERN ENTRANCE IS SHOWN LESS THAN THE |
| REQUIRED 24 FEET IN WIDTH. NINETY DEGREE PARKING SPACES |
| ARE REQUIRED TO HAVE A FULL 24 FEET OF BACK-UP SPACE. |
| THIS PLANS NEED TO CLEARLY SHOW THAT THE 24 FEET IS |
| PROVIDED. |
| |
| 3) PER THE SPECIAL USE PERMIT, ALL GROUND LEVEL |
| MECHANICAL EQUIPMENT MUST BE ON THE NORTH SIDE OF THE |
| BUILDING. |
| |
| 4) PLEASE DESCRIBE WHO THE LOUNGE IS FOR. THIS IS WAS |
| NOT INCLUDED ON THE PLANS APPROVED AS PART OF THE |
| SPECIAL USE PERMIT. |
| |
| 5) THE SIGN REQUIRES A SEPARATE PERMIT WITH PLANS. |
| |
| 6) THE SITE LIGHTING REQUIRES A SEPARATE PERMIT WITH |
| PLANS. INCLUDE PHOTOMETRICS. PLEASE REMEMBER THAT THE |
| POLES MUST BE SETBACK A MINIMUM OF FIVE (5) FEET FROM |
| THE PROPERTY LINES. THIS NEEDS TO BE CLEARLY SHOWN ON |
| THE PLANS. |
| |
| 7) PLEASE NOTE THE FOLLOWING CONDITION FROM THE SPECIAL |
| USE APPROVAL: |
| |
| THE FOLLOWING MUST BE ADDRESSED PRIOR TO ISSUANCE OF |
| CONSTRUCTION AUTHORIZATION INCLUDING BUILDING PERMITS |
| AND ENGINEERING DEVELOPMENT APPROVAL: |
| A. AN EROSION AND SEDIMENT CONTROL PLAN WILL BE |
| REQUIRED WITH THE ENGINEERING PERMIT APPLICATION |
| SUBMITTAL. |
| B. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL |
| BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. |
| C. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC |
| CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF |
| WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL |
| WORK PROPOSED. |
| D. SHOW THE NEAREST FIRE HYDRANT TO THIS SITE ON THE |
| FINAL UTILITY PLAN. FIRE HYDRANT FLOW TEST DATA FROM |
| EXISTING FIRE HYDRANT WILL BE REQUIRED PART OF THE PLAN |
| SUBMITTAL. SHOW HYDRANT FLOW TEST DATA RESULT ON THE |
| PLANS. |
| E. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE |
| WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN |
| AN EASEMENT WITHIN THE PROPERTY. |
| F. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL |
| EXISTING UTILITIES ON S. DIXIE HWY INCLUDING BUT NOT |
| LIMITED TO WATER, SEWER, GAS, UNDERGROUND ELECTRIC |
| CONDUITS, VALVES, ETC. PLEASE IDENTIFY THE SOURCE OF |
| THE AS-BUILT INFORMATION UTILIZED FOR THE POTABLE |
| WATER, SANITARY SEWER, AND STORM SEWER DESIGN. |
| G. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE |
| THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM |
| BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD |
| FREE." |
| H. THE CITY'S MILL AND RESURFACING LIMITS ARE 50 FEET |
| ON EACH SIDE OF THE TRENCH CUT. FDOT MAINTAINS DIXIE |
| HIGHWAY SO ITS REQUIREMENTS FOR MILL AND RESURFACING |
| SHOULD BE FOLLOWED AND SHOWN ON THE ENGINEERING PLANS. |
| |
| 8) THE BICYCLE RACK AND THE FRON PLAZA HARDSCAPE |
| REQUIRE A SEPARATE PERMIT, WITH PLANS. |
| |
| 9) THE REPLACEMENT FENCE AND GATE REQUIRE A SEPARATE |
| PERMIT, WITH PLANS. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |