2018-12-18 14:02:18 | PLUMBING COMMEMTS: DENIED |
| 1. THE BUILDING CODE INFORMATION INDICATES THE |
| OCCUPANCY TYPE AS A GROUP S-2 OCCUPANCY, IS THIS USE |
| FOR STORAGE OF AUTOMOBILES OR IS THIS USAGE FOR |
| AUTOMOBILE REPAIR SHOP. THE LIFE SAFETY PLAN SHOWS A |
| LOUNGE IN THIS BUILDING, IT WOULD APPEAR THIS MAYBE A |
| MOTOR VEHICLE SHOWROOM WHICH WOULD MAKE THE OCCUPANCY |
| TYPE BUSINESS, SEE FBC 304.1. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED TO DETERMINE OCCUPANCY TYPE. |
| A) IF THIS IS BUSINESS OCCUPANCY OR MERCANTILE AS NOTED |
| IN TABLE 403.1 THEN PER FBC PL 416.5, TEMPERED WATER |
| FROM LAVATORIES SHALL BE PROVIDED FOR CUSTOMERS, |
| PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED |
| THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE |
| THAT CONFORMS TO ASSE 1070 OR CSA B125.3. |
| 2. PROVIDE DRINKING FOUNTAIN PER FBC PL TABLE 403.1 |
| 3. PROVIDE SERVICE SINK PER FBC PL TABLE 403.1 |
| 4. IS THERE A BATTERY STORAGE OR CHARGING AREA IN THE |
| FACILITY? IF SO, REFLECT ON PLANS AND PROVIDE EMERGENCY |
| EYEWASH IN ACCORDANCE WITH OSHA STANDARD 29 CFR |
| 1910.151(C), AND FBC PL 411. |
| 5. PROVIDE WHA AT DISHWASHER |
| 6. RE: ADA COMPLIANT SHOWER: PROVIDE CUT SHEET OF |
| SCHEDULED SHOWER FREEDOMLINE #2271 FOR REVIEW OF FBC |
| ACC CHAPTER 6 COMPLIANCE INCLUDING BUT NOT LIMITED TO |
| LOCATION OF SHOWER CONTROL, SHOWER HEAD, SEAT AND GRAB |
| BARS PER WPB FBC 107.2.1 |
| 7. PER FBC PL TABLE 403.1 (S-2 OCCUPANCY), PROVIDE MALE |
| AND FEMALE TOILET ROOM FACILITIES. |
| |
| END OF COMMENTS |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |