2018-11-26 09:41:20 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18100354 |
| 11/26/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M2.0: RECIRCULATION OF AIR FROM THE GARAGE |
| INTO THE LOUNGE AREA AND THE TOILET ROOM IS PROHIBITED |
| PER TABLE 403.3.1.1 FOOTNOTE B FBC M. |
| |
| 2) M2.0: SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE CO AND NO2 SENSORS |
| AND THE CONTROL PANEL- SECTION 404.1 FBC M. |
| |
| 3) M2.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION |
| 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE |
| SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| SUPPLY AIR. |
| |
| 4) M1.0: PROVIDE THE MINIMUM VENTILATION RATE FOR THE |
| LOUNGE ROOM- TABLE 403.3.1.1 FBC M. |
| |
| 5) M2.0: PLEASE IDENTIFY ALL APPLIANCES IN THE KITCHEN |
| AND PROVIDE A EQUIPMENT LIST. SUBMIT MANUFACTURER |
| SPECIFICATIONS FOR ALL COOKING APPLIANCES AND EXHAUST |
| HOODS ( IF APPLICABLE). PLEASE NOTE THAT SEPARATE |
| PERMITS ARE REQUIRED FOR COMMERCIAL KITCHEN EXHAUST AND |
| FIRE SUPPRESSION SYSTEMS- SECTION 107.1 WPB. |
| |
| 6) M2.0: PROVIDE CONSTRUCTION DETAILS FOR THE CONDENSER |
| PADS, AND INDICATE THE TYPE AND SIZE OF ANCHOR BOLT FOR |
| ATTACHING THE UNITS TO THE PADS- SECTION 301.15 FBC M. |
| |
| 7) M1.0: THE MIAMI-DADE NOA #12-0830.07 FOR THE LOUVERS |
| IS EXPIRED, AND HAS BEEN REPLACED WITH #16-0201.02. |
| PLEASE CORRECT THE NOTES ON THE PLAN AND SUBMIT THE |
| NOA. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |