2018-11-26 09:41:201ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18100354
 11/26/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.0: RECIRCULATION OF AIR FROM THE GARAGE
 INTO THE LOUNGE AREA AND THE TOILET ROOM IS PROHIBITED
 PER TABLE 403.3.1.1 FOOTNOTE B FBC M.
  
 2) M2.0: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE CO AND NO2 SENSORS
 AND THE CONTROL PANEL- SECTION 404.1 FBC M.
  
 3) M2.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION
 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE
 APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE
 SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 4) M1.0: PROVIDE THE MINIMUM VENTILATION RATE FOR THE
 LOUNGE ROOM- TABLE 403.3.1.1 FBC M.
  
 5) M2.0: PLEASE IDENTIFY ALL APPLIANCES IN THE KITCHEN
 AND PROVIDE A EQUIPMENT LIST. SUBMIT MANUFACTURER
 SPECIFICATIONS FOR ALL COOKING APPLIANCES AND EXHAUST
 HOODS ( IF APPLICABLE). PLEASE NOTE THAT SEPARATE
 PERMITS ARE REQUIRED FOR COMMERCIAL KITCHEN EXHAUST AND
 FIRE SUPPRESSION SYSTEMS- SECTION 107.1 WPB.
  
 6) M2.0: PROVIDE CONSTRUCTION DETAILS FOR THE CONDENSER
 PADS, AND INDICATE THE TYPE AND SIZE OF ANCHOR BOLT FOR
 ATTACHING THE UNITS TO THE PADS- SECTION 301.15 FBC M.
  
 7) M1.0: THE MIAMI-DADE NOA #12-0830.07 FOR THE LOUVERS
 IS EXPIRED, AND HAS BEEN REPLACED WITH #16-0201.02.
 PLEASE CORRECT THE NOTES ON THE PLAN AND SUBMIT THE
 NOA.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  