2018-11-08 15:50:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION SHOWS A DEMAND LOAD FOR KITCHEN
 EQUIPMENT AT 50%. I SEE NO KITCHEN EQUIPMENT THAT WOULD
 QUALIFY FOR A DEMAND LOAD REDUCTION. ALSO, A REDUCTION
 OF 50% FOR KITCHEN EQUIPMENT DOES NOT EXIST. PROVIDE
 CORRECTION. NEC 220.56
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 3. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 IN GARAGE, INCLUDING CORD REELS. NEC 511.12
 4. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 WITHIN 6 FEET OF A SINK. NEC 210.8
 5. GENERAL NOTE 1 ON SHEET E4.0 STATES THAT ALL
 CONDUITS SHALL BE RUN IN CAVITY OF PURLIN. THIS IS A
 CODE VIOLATION. PROVIDE CORRECTION. NEC 300.4(E)
 6. PROVIDE CLARIFICATION FOR FIRE SPRINKLER FEED, WILL
 THERE BE A FIRE SPRINKLER PUMP, OR IS THE WATER
 PRESSURE FROM CITY ACCEPTABLE AND A FIRE PUMP WILL NOT
 BE REQUIRED? IF FIRE PUMP REQUIRED, INCLUDE ELECTRICAL
 DETAILS. WPB FBC 107.2.1
 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved