Plan Review Notes
Plan Review Notes For Permit 18100337
Permit Number 18100337
Review Stop P
Sequence Number 2
Notes
Date Text
2018-11-26 06:15:491) THERE ARE COPIES OF THE SAME SHEET E-1 THAT SHOW TWO
 DIFFERENT DETAILS ON THE PLANS AND SEVERAL LOOSE PAGES.
 THERE ARE ALSO TWO COPIES OF A SHEET M.2. SUBMIT TWO
 COMPLETE SETS OF PLANS THAT CONTAIN ALL THE DRAWINGS
 FOR THIS PROJECT FOR REVIEW. WPB AMEND. TO FBC SEC.
 107.1.
 2) COPIES OF A PUMP PERFORMANCE CURVE, NUMBERING SYSTEM
 AND A DIMENSIONS AND WEIGHT SHEET HAVE BEEN SUBMITTED
 FOR REVIEW. EXPLAIN HOW THIS COMPLIES WITH THE REVIEW
 COMMENT FOR SUBMITTING TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMPS. THERE ARE MORE THAN 4
 PAGES IN THE MANUFACTURER'S SPECIFICATIONS. WPB AMEND.
 TO FBC SEC. 107.2.1. SUBMIT TWO CCOMPLETE COPIES OF THE
 MANUFACTURER'S PUMP SPECIFICATIONS FOR REVIEW. 2ND
 REQUEST.
 3) PRESSURE REDUCING VALVES ARE REQUIRED IF THE STSTIC
 WATER PRESSURE WITHIN THE BUILDING EXCEEDS 80 PSI.
 PRESSURE REDUCING VALVES SHALL COMPLY WITH 2017 FBC
 SEC. 604.8. INDICATE ON THE PLANS WHAT THE PROPOSED
 STATIC PRESSURE OF THE SYSTEM WILL BE AND IF THE
 EXISTING SYSTEM IS EQUIPPED WITH PRESSURE REDUCCING
 VALVES OR IF PRESSURE REDUCING VALVES WILL NEED TO BE
 INSTALLED. WPB AMEND TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW