2018-11-26 06:15:49 | 1) THERE ARE COPIES OF THE SAME SHEET E-1 THAT SHOW TWO | | DIFFERENT DETAILS ON THE PLANS AND SEVERAL LOOSE PAGES. | | THERE ARE ALSO TWO COPIES OF A SHEET M.2. SUBMIT TWO | | COMPLETE SETS OF PLANS THAT CONTAIN ALL THE DRAWINGS | | FOR THIS PROJECT FOR REVIEW. WPB AMEND. TO FBC SEC. | | 107.1. | | 2) COPIES OF A PUMP PERFORMANCE CURVE, NUMBERING SYSTEM | | AND A DIMENSIONS AND WEIGHT SHEET HAVE BEEN SUBMITTED | | FOR REVIEW. EXPLAIN HOW THIS COMPLIES WITH THE REVIEW | | COMMENT FOR SUBMITTING TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE PUMPS. THERE ARE MORE THAN 4 | | PAGES IN THE MANUFACTURER'S SPECIFICATIONS. WPB AMEND. | | TO FBC SEC. 107.2.1. SUBMIT TWO CCOMPLETE COPIES OF THE | | MANUFACTURER'S PUMP SPECIFICATIONS FOR REVIEW. 2ND | | REQUEST. | | 3) PRESSURE REDUCING VALVES ARE REQUIRED IF THE STSTIC | | WATER PRESSURE WITHIN THE BUILDING EXCEEDS 80 PSI. | | PRESSURE REDUCING VALVES SHALL COMPLY WITH 2017 FBC | | SEC. 604.8. INDICATE ON THE PLANS WHAT THE PROPOSED | | STATIC PRESSURE OF THE SYSTEM WILL BE AND IF THE | | EXISTING SYSTEM IS EQUIPPED WITH PRESSURE REDUCCING | | VALVES OR IF PRESSURE REDUCING VALVES WILL NEED TO BE | | INSTALLED. WPB AMEND TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|