Plan Review Notes For Permit 18100323 |
Permit Number |
18100323 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-12 13:35:32 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NEED TO SHOW SIZE OF BRANCH CIRCUITS | | | | E3701.2BRANCH-CIRCUIT AND FEEDER AMPACITY. | | BRANCH-CIRCUIT AND FEEDER CONDUCTORS SHALL HAVE | | AMPACITIES NOT LESS THAN THE MAXIMUM LOAD TO BE SERVED. | | WHERE A BRANCH CIRCUIT | | OR A FEEDER SUPPLIES CONTINUOUS LOADS OR ANY | | COMBINATION OF CONTINUOUS AND NONCONTINUOUS LOADS, THE | | MINIMUM BRANCH-CIRCUIT OR | | FEEDER CONDUCTOR SIZE, BEFORE THE APPLICATION OF ANY | | ADJUSTMENT OR CORRECTION FACTORS, SHALL HAVE AN | | ALLOWABLE AMPACITY EQUAL TO OR | | GREATER THAN THE NONCONTINUOUS LOAD PLUS 125 PERCENT OF | | THE CONTINUOUS LOAD. [210.19(A)(1)(A) AND | | 215.2(A)(1)(A)] | | | | NEED TO SHOW LOCATION OF EQUIPMENT INSIDE AND OUTSIDE. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS | | | | REVIEWS ARE COMPLETE; HOWEVER YOUR APPLICATION HAS NOT | | BEEN APPROVED. YOU CAN VIEW THE COMMENTS BY SELECTING | | THE PLAN REVIEWS TAB AT: HTTP://ONESTOPSHOP.WPBGOV.COM/ | | EGOVPLUS/PERMIT/PERM_STATUS.ASPX |
|