Plan Review Notes For Permit 18100323
Permit Number 18100323
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-12 13:35:32FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW SIZE OF BRANCH CIRCUITS
  
 E3701.2BRANCH-CIRCUIT AND FEEDER AMPACITY.
 BRANCH-CIRCUIT AND FEEDER CONDUCTORS SHALL HAVE
 AMPACITIES NOT LESS THAN THE MAXIMUM LOAD TO BE SERVED.
 WHERE A BRANCH CIRCUIT
 OR A FEEDER SUPPLIES CONTINUOUS LOADS OR ANY
 COMBINATION OF CONTINUOUS AND NONCONTINUOUS LOADS, THE
 MINIMUM BRANCH-CIRCUIT OR
 FEEDER CONDUCTOR SIZE, BEFORE THE APPLICATION OF ANY
 ADJUSTMENT OR CORRECTION FACTORS, SHALL HAVE AN
 ALLOWABLE AMPACITY EQUAL TO OR
 GREATER THAN THE NONCONTINUOUS LOAD PLUS 125 PERCENT OF
 THE CONTINUOUS LOAD. [210.19(A)(1)(A) AND
 215.2(A)(1)(A)]
  
 NEED TO SHOW LOCATION OF EQUIPMENT INSIDE AND OUTSIDE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS
  
 REVIEWS ARE COMPLETE; HOWEVER YOUR APPLICATION HAS NOT
 BEEN APPROVED. YOU CAN VIEW THE COMMENTS BY SELECTING
 THE PLAN REVIEWS TAB AT: HTTP://ONESTOPSHOP.WPBGOV.COM/
 EGOVPLUS/PERMIT/PERM_STATUS.ASPX